Troubleshooting SiE 00-07 3.32 Excessive Number of Indoor Units Remote Controller Display Supposed Causes UA Excess of connected indoor units Defect of outdoor unit PC board (A1P) Troubleshooting The total of indoor units displaying "UA" and indoor units connected to the same refrigerant system is 20 or 32 units or less.∗ NO There are too many indoor units within the same refrigerant system. YES Push and hold the RESET button on the outdoor unit PC board for 5 seconds. Does a malfunction occur? YES NO Normal Replace outdoor unit PC board (A1P). (VF059) The number of indoor units that can be connected to a single outdoor unit system depends on the type of outdoor unit. ∗ RSXYP16~20KJY1 ··· 20 units RSXYP24~30KJY1 ··· 32 units 154 Troubleshooting R-407C PLUS Series