Set Point 2 Reset. Select OnOF or Hold.
OnOF
Output will automatically reset when process passes
back through SP2d.
HoLd
Manual Reset. Reset (acknowledge) by simultaneously
INDEX & DOWN ARROW keys
pressing the
for 3 seconds.
S2Pi
Set Point 2 Power Interrupt. Select On or OFF.
On
Alarm Power Interrupt is On. Output will automatically
reset on power-up if no alarm condition exists.
OFF
Alarm Power Interrupt is OFF. Output will be in the
alarm condition on power-up regardless of condition of
process.
S2iH
Set Point 2 Inhibit: Select On or OFF.
On
Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF
Alarm Inhibit is OFF.
S2LP
Set Point 2 Lamp: Select O on or OoFF.
O on
Lamp ON when Output is ON.
OoFF
Lamp OFF when Output is ON.
ALARM TYPE AND ACTION (if alarm function is present)
Caution: In any critical application where failure could
cause expensive product loss or endanger personal safety,
a redundant limit controller is required.
When setting an alarm value for an absolute alarm (A1t = AbS), simply set
the value at which the alarm is to occur.
When setting the alarm value for a deviation alarm (A1t = dE), set the difference in value from the Set Point desired. For example if a low alarm is
required to be 5 degrees below the Set Point, then set A1Lo to -5. If a high
alarm is required 20 degrees above the Set Point, then set A1Hi to +20. If
the Set Point is changed, the alarm will continue to hold the same relationship as originally set.