Download cg3-uv
Transcript
"CG3-UV" SERIES VENTILATOR PRINCIPLE OF OPERATION INTERNAL FIRE MODE—For CG3-UV and CG3-UV-FDT only! Automatic internal fire protection is accomplished by the action of the thermostat(s), which are located at the point where the ductwork joins the ventilator. When the temperature of the conveying airstream, which must pass over the thermostats, reaches 250°F, the system is activated, and the following occurs: 7. Then the digital display reads "Fire In Hood, Notify Fire Department". This display stays on until the thermostat cools down below 250°F. 7. A red light on the Command Center illuminates. 8. On the C-6000-UV control: dry contacts A1 & A2 will CLOSE and dry contact Q1 & Q2 will OPEN. 9. Upon cooling of the thermostat below 250oF, the Cool Down Cycle starts. The water continues to spray during the Cool Down Cycle (2 minutes). The damper moves to the exhaust position. (N/A on CG3-UV-FDT) 1. The damper begins closing back to the fire position, position 3 as shown in Fig.4—stopping the combustionsupporting, natural draft through the ventilator and creating a fire barrier to contain the fire in the kitchen. (N/A on CG3UV-FDT) 10.While in the cool down cycle the digital display reads "Cool Down Cycle, xxx sec. to end". xxx is the countdown in seconds until the wash turns off. The damper moves to the exhaust position. 2. The UV lamps are shut off. 3. The exhaust fan serving the ventilator is shut off. The supply fan is also shut off. 11.At the end of the cool down cycle the wash turns off and the digital display reads "Fan Off 12:00 (actual time), Start Fan>F1". The damper closes to the wash position. (N/A on CG3-UV-FDT) 4. Fire-smothering water spray is released into the interior of the ventilator through the spray nozzles. 5. The digital display reads "Fire In Hood, Fan Off, Wash On" for approximately 5 seconds. NOTE: The water may be shut off prior to the end of the 2 minute cool down cycle by pushing the “Exit” button on the C-6000-UV Command Center. After the water has shut off, the damper remains in the wash position until the “Start Fan” button is pushed. Starting the Exhaust Fan 6. Then the digital display reads "Fire In Hood, Damper Closing" for approximately 5 seconds. CAUTION: In case of severe fire the thermostats located in the plenum will activate. As a precautionary measure, it is recommended that the thermostats be replaced. WATER SUPPLY FROM CONTROL CABINET FIRE QUENCHING WATER SPRAY WATER BARRIER DAMPER CLOSED BACK TO THE FIRE POSITION DRAIN LINE SURFACE FIRE PROTECTION NOZZLE (OPTIONAL) FIG. 4 FIRE CYCLE 8