Download Single Packaged Air Conditioner
Transcript
Electronic parts Troubleshooting Guide Possible trouble 7 Is the indoor fan operation? : No humidifier operation performed. NO 1. Press cooling or fan operation or heater operation key. YES Is the HUMID LCD "ON"? NO 1. Press humidifier Key. YES Is the output voltage of IC03D on the MAIN PCB DC5V? NO 1. Check or exchange IC03D. IC02D on the MAIN PCB. YES Is the output voltage of IC01M's 10PIN on the MAIN PCB 0V? NO 1. Check or exchange IC01M. YES Is the voltage between 1PIN of CN-HUMID and NEUTRAL 220V? NO 1. Check or exchange RY3. YES Is the magnetic contactor for humidifier ON? NO 1. Check the wiring or Magnetic contactor. 2. Exchange Magnetic contactor. YES Check the humidifier. Service Manual 21