Transcript
Error Contents Error code Plus: 113 (Main) 125 (Sub1) 137 (Sub2) 166 (Sub3) Plus II: 11˧131 12˧132 13˧133 14˧134 Outdoor unit liquid pipe (condenser) temperature sensor error Error code Meaning Abnormal sensor resistance value (Open/Short) Error Contents Plus: 114 (Main sub-cool inlet) 115 (Main sub-cool outlet) 126 (Sub1 sub-cool inlet) 127 (Sub1 sub-cool outlet) 138 (Sub2 sub-cool inlet) 139 (Sub2 sub-cool outlet) 167 Sub3 sub-cool inlet) Outdoor unit sub168 (Sub3 sub-cool outlet) cooling inlet / outlet temperature sensor Plus II: error 11˧141(sub-cool inlet) 12˧142 13˧143 14˧144, 11˧151(sub-cool outlet) 11˧152 11˧153 11˧154 Main Causes 1. Defective temperature sensor connection 2. Temperature sensor defect(Open / Short) 3. Outdoor unit main PCB defect Meaning Abnormal sensor resistance value (Open/Short) Main Causes 1. Defective temperature sensor connecter connection 2. Temperature sensor defect(Open / Short) 3. Outdoor unit main PCB defect Error diagnosis and countermeasure flow chart Is temperature sensor connector connections are normal? No • Sub-cool circuit in the outdoor unit Check and correct connection Yes Is the value of temperature sensor resistance normal?* No Replace sensor (Plus) Yes Replace outdoor unit PCB * Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error (Plus II) Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value according to outdoor unit temperature by referring below table (·5% tolerance) Air temperature sensor: 10 = 20.7༮ : 25= 10༮ : 50= 3.4༮ Pipe temperature sensor: 10 = 10༮ : 25= 5༮ : 50= 1.8༮ - Liquid pipe temp sensor - Sub-cool inlet temp sensor 124 - Sub-cool outlet temp sensor