Error Contents
Error code
Plus:
113 (Main)
125 (Sub1)
137 (Sub2)
166 (Sub3)
Plus II:
11˧131
12˧132
13˧133
14˧134
Outdoor unit
liquid pipe
(condenser)
temperature
sensor error
Error code
Meaning
Abnormal sensor
resistance value
(Open/Short)
Error Contents
Plus:
114 (Main sub-cool inlet)
115 (Main sub-cool outlet)
126 (Sub1 sub-cool inlet)
127 (Sub1 sub-cool outlet)
138 (Sub2 sub-cool inlet)
139 (Sub2 sub-cool outlet)
167 Sub3 sub-cool inlet)
Outdoor unit sub168 (Sub3 sub-cool outlet)
cooling inlet / outlet
temperature sensor
Plus II:
error
11˧141(sub-cool inlet)
12˧142
13˧143
14˧144,
11˧151(sub-cool outlet)
11˧152
11˧153
11˧154
Main Causes
1. Defective temperature sensor connection
2. Temperature sensor defect(Open / Short)
3. Outdoor unit main PCB defect
Meaning
Abnormal sensor
resistance value
(Open/Short)
Main Causes
1. Defective temperature sensor connecter
connection
2. Temperature sensor defect(Open / Short)
3. Outdoor unit main PCB defect
Error diagnosis and countermeasure flow chart
Is temperature sensor
connector connections
are normal?
No
• Sub-cool circuit in the
outdoor unit
Check and correct connection
Yes
Is the value of temperature
sensor resistance normal?*
No
Replace sensor
(Plus)
Yes
Replace outdoor unit PCB
* Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error
(Plus II)
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (·5% tolerance)
Air temperature sensor: 10୅ = 20.7༮ : 25୅= 10༮ : 50୅= 3.4༮
Pipe temperature sensor: 10୅ = 10༮
: 25୅= 5༮ : 50୅= 1.8༮
- Liquid pipe temp sensor
- Sub-cool inlet temp sensor
124
- Sub-cool outlet temp sensor