FLOW CHART E. OUTPUT VOLTAGE TOO HIGH, TOO LOW, OR UNSTABLE (TRANSFORMER VOLTAGE REGULATOR) Many iroubieshooting procedures present hazards that can resuit in severe personal injury or b % ! l death. Only qualified senice personnel knowledge of fuels,eieciricity, and macbimry hazads should perform service procedures. Review safety precautions on inside cover page. witt, START Set r/min per instructions in appropriate engine manual. Is engine running stable and at correct r/min? Are there broken wires or loose connections to any AC regulator components? Apply load to generator and then remove. Is voltage across generator leads S1 and S2 60 VAC 2 5 percent? + no * Repair as required. Test stator assembly per TEST [K]. Replace if bad. 1I Test transformer T21 per TEST [N]. Replace if bad. , Test exciter stator per TEST [HI Replace if bad, 1 Test rotor assembly per TEST [J]. Replace i f bad. 6-6 Redistribution or publication of this document by any means, is strictly prohibited.