Download RX 26 BF
Transcript
IT ES 2.8 PT ø 80 SEPARATE PIPES INSTALLATION TABLE 1 Accessories ø 80 When installing the pipes, follow closely the requirements of the current standards, as well as the following practical indications: GB – With direct intake from outside, when the pipe is longer than 1 m, you are recommended to insulate the piping so as to prevent formation of dew on the outside of the piping during certain periods of the year. – With the outlet pipe outside the building or in cold indoor environments, insulation is necessary to prevent burner failure while starting. In such cases, provide for a condensate-collector system on the piping. – If a segment of the flue passes through a flammable wall, this segment must be insulated with a 30 mm thick glass wool pipe insulator, with a density of 50 kg/m3. The maximum overall length of the intake and exhaust ducts depends on the head losses of the single fittings installed and must not exceed than 6,00 mm H2O. 90° elbow MF 45° elbow MF Extension L. 1000 (horizontal) Extension L. 1000 (vertical) Outlet terminal Intake terminal Manifold Roof outlet terminal L. 1390 Tee condensation outlet Load loss (mm H2O) Outlet Roof out. Intake 0,50 – 0,40 – 0,40 – 0,30 – 0,40 – – – – – – 0,60 1,10 – Example of allowable installation calculation in that the sum of the head losses of the single fittings is less than 6,00 mm H2O: 6 meter horizontal pipe ø 80 x 0,20 6 meter horizontal pipe ø 80 x 0,40 n° 2 90° elbows ø 80 x 0,30 n° 2 90° elbows ø 80 x 0,50 n° 1 terminal ø 80 Total head loss Intake 1,20 – 0,60 – 0,10 1,90 Outlet – 2,40 – 1,00 0,40 + 3,80 = 5,7 mm H2O The intake diaphragm is to be removed with this maximum loss of load. KEY 1 Blank flange 2 Outlet flange 3 Screw 4 Sponge sheath ø 125/95 5 Intake collar 6 Intake diaphragm 7 Sponge sheath ø 100/78 During installation use only original SIME accessories and make sure that the connection is carried out properly, as indicated in the accessory instructions. For head losses in the fittings, refer to Table 1. 2.8.1 Intake 0,30 0,20 0,20 0,30 – 0,10 0,30 – – Separate flue kit (fig. 4) The required intake diaphragm is supplied with the separate duct kit code 8089905, according to the maximum load allowed in both ducts, as indicated in fig. 4/a. 1 6 2.8.2 Outlet systems The diagrams in fig. 5 illustrate a number of examples of different types of separate outlets. N° diaphragm sectors to remove 1 3 4 6 Remove the diaphragm 4 2 7 5 3 Total load loss mm H2O 0 ÷1 0 1 ÷2 9,8 2 ÷3 19,6 3 ÷4 29,4 4 ÷6 39,2 Pa ÷ ÷ ÷ ÷ ÷ Fig. 4 9,8 19,6 29,4 39,2 58,8 DIAPHRAGM SECTOR Fig. 4/a 40