Manuales del programador Página 58 de 107 Error Number (Hex) 80 Error Tag E_ILLEGAL_DIGIT Description One or more characters sent in the command could not be correctly converted to a digit (hex or decimal). 81 E_BAD_ADDRESS The command is valid, but the addressed module does not support the command received. 82 E_INBUF_FRMERR The FieldPoint network module detected a serial framing error in the command. The command was ignored. 83 E_NO_MODULE The addressed module does not exist. 84 E_INV_CHNL One or more channels specified in the command either do not exist or do not support the operation specified. The command was ignored. 85 E_INV_RANGE One or more ranges specified in the command either do not exist or do not support the setting specified. The command was ignored. 86 E_INV_ATTR One or more attributes specified in the command either do not exist or do not support the setting specified. The command was ignored. 88 E_HOTSWAP The module has been hot-swapped since it was last sent a command. This response is sent only if the network module is enabled to report hot-swaps, and if the hot-swap occurred after hot-swap reporting mode was enabled. The command was ignored. This error number can be sent in response to a standard command if you have enabled hot-swap reporting for the bank. 89 E_ADDR_NOT_SAME The module addressed by the Resend Last Response is not the same as the module addressed by the previous command. 8A E_NO_RESEND_BUF The response to the last command is unavailable 8B E_HW_FAILURE An irrecoverable fault has occurred. 8C E_UNKNOWN An unidentifiable error condition has occurred. Tabla 2.6 Extended Error Responses Conjunto de drivers para tarjetas de adquisición de señales bajo Linux