Communication settings with Micrologic E
Micrologic 6.0 E
Activate tree navigation mode.
and the
buttons for
Simultaneously press the
three seconds. A series of four screens are displayed
for configuration of the Modbus communication.
digital display
navigation buttons
Screen 1 Address
The default Modbus address for the device is 47. The
screen displays AdXX when the existing address for the
communication module is XX.
A closed padlock icon displayed indicates that the value
is locked.
Press on the
button to open the padlock and
display the first digit (e.g. 4) flashing, ready to be
modified.
Briefly press on the
button to increment in a loop
the value up to the new setting.
Briefly press on the
button to validate this value
and display the second digit (e.g. 7) flashing, ready
to be modified.
Briefly press on the
button to increment in a loop
the value up to the new setting.
button to validate the new
Briefly press on the
Modbus address (the two choosen digits) whose
display becomes permanent. The padlock is still open.
button to padlock this
Briefly press again on the
value and display screen 2.
menu
press simultaneously
DB12675
k
5100512864A-02
(see pages 47)