Download DLS VAV SYSTEM
Transcript
IR RECEIVER MOTORIZED DAMPER 10” MOTORIZED DAMPER 10” ROOM #2 ON 12 ON 12 Dip sw #3 - Parallel dampers/grilles operation room. #1+#2 dip #4 - round or rectangular damper 1234 ROOM #1 ON IR TRANSMITER Operation When Zone Controller is NOT connected to the Air condition When the VAV SYSTEM controller is not connected to the air condition, all dampers and Grills will be fully open. The Dampers and Grills will remain open, no matter which command is received from the handheld remote control. The Indication to this situation, the green LED on each I/R receiver will blink every half a second. (Half second ON and Half second OFF). Operation in Fan Only (ventilation) Mode When the air condition receives Fan Only command, the VAV SYSTEM zone control will operate same as in COOL mode. Operation in DRY Mode When the air condition receives DRY command, the VAV SYSTEM zone control will operate same as in COOL mode. Operation in AUTO Mode When the air condition receives AUTO command, the VAV SYSTEM zone control will open all dampers to full open position. Except those dampers that received OFF command from the room handheld remote control. E n g lis h 11