5 Parameter settings
The parameters displayed in the PARA menu branch are partly set via the guided commissioning.
Additional Configurations with further parameter settings are described in the operating instructions manual.
Control Level 28 - The brief instructions describe the parameters in control level 1. The parameters of the higher control levels 2 or 3 are described in the operating instructions and should be
set up by expert operators only.
Setting:
1 ... 3
Configuration 30 - The basic function of the control inputs and outputs as well as the assignment
of the software modules is selected by the configuration. The selection is made during the guided
commissioning.
Setting:
110 - sensor-less control with U/f characteristic for speed regulation in a great
number of standard applications
410 - sensor-less, field-oriented control, for applications with a high functionality
and dynamics
Program(ming) 34 - The factory settings of all parameters is restored or a fault message is acknowledged (alternative to signal at digital input S1IND).
Setting:
4444 Activate factory settings
123
Acknowledge fault message
Motor type 369 – Setting of connected motor or transformer. The verification of the entered
rated values and the guided commissioning are carried out on the basis of the parameterized motor type.
0Unknown
The motor is not a standard type.
Setting:
1Asynchronous Three-phase asynchronous motor, squirrel cage
2Synchronous Three-phase synchronous motor
3Reluctance
Three-phase reluctance motor
10 Transformer
Transformer with three primary windings
Rated Voltage 370 - Enter the voltage indicated on the type plate of the asynchronous motor.
Setting:
60.0 V ... 800.0 V
Rated Current 371 - Enter the rated current indicated on the type plate of the asynchronous mo-
tor.
Setting:
0.01⋅IFIN ... 10⋅o⋅IFIN
Rated Speed 372 – Enter the motor speed (at rated frequency) indicated on the type plate of the
asynchronous motor.
Setting:
96 min-1 ... 60000 min-1
Rated Cosinus Phi 374 – Enter the cos (ϕ) value indicated on the type plate of the asynchronous
motor.
Setting:
0.01 ... 1.00
Rated Frequency 375 – Enter the rated frequency (at parameterized rated speed) indicated on
the type plate of the asynchronous motor.
Setting:
10.00 ... 1000.00
Rated Mech. Power 376 - Enter the power (in kW) indicated on the type plate of the asynchronous motor.
Setting:
0.1⋅PFIN ... 10⋅PFIN
40