Fig. 15 Parameter page 2
Pressing the
key in the second page will display the third page (Fig. 16)
containing the following parameters:
Safety temperature pump ON – If the normal or quick stop procedure was
initiated and the boiler temperature is higher than set for this parameter, the
circulation pump will start;
Safety temperature pump OFF – After temperature decreases below the level set
for this parameter and the boiler is in the Stop state, the recirculation pump
stops;
Use boiler as cascade master – This parameter will be activated only if the unit
operates in a cascade arrangement with other heating units and its boiler is used
as master boiler;
Start second heating unit after – If the heating unit operates in cascade with
other units and is set as master boiler, this will set the time for starting the
secondary boiler if the master unit fails to bring the water in the system to the
set parameters;
Maximum exhaust temperature for ignition – The second condition for starting
the unit. If the exhaust temperature exceeds the limit set for this parameter, the
exhaust fan will start and ignition will be initiated only after the exhaust
temperature decreases below this limit;
Exhaust temperature (alarm) – If exhaust temperature exceeds this limit, an
alarm will be displayed;
Exhaust temperature stops boiler – If exhaust temperature reaches this limit, the
unit will stop, an alarm message will be displayed and the user must contact the
17