CHAPTER 7 CALIBRATION
7.6 Checking Indication Accuracy
· After calibrating input, make sure that you check indication accuracy to
make sure that the E5AK controller has been correctly calibrated.
· Operate the E5AK controller in the PV/SP monitor (level 0 mode) mode.
· Check the indication accuracy at the upper and lower limits and midpoint.
F Thermocouple
AC100-240V ~
(AC/DC24V )
SOURCE
· Preparation
The following figure shows the required device connection. Make sure
that the E5AK controller and cold junction compensator are connected
by a compensating conductor for the input type that is to be used during
actual operation.
10
9
30 31 32 20
29
19
8
28
18
7
27
17
6
26
16
5
25
15
4
24
14
3
23
13
2
22
12
1
21 33
11
Cold junction
compensator
STV
Compensation
conductor
· Operation
Make sure that the cold junction compensator is at 0_C, and set STV output to the voltage equivalent to the starting power of the check value.
F Platinum resistance thermometer
· Preparation
The following figure shows the required device connection.
AC100-240V ~
(AC/DC24V )
SOURCE
9
30 31 32 20
19
29
8
28
18
10
7
27
17
6
26
16
5
4
25
24
15
14
3
23
13
2
22
12
1
21 33
11
6-dial
· Operation
Set the 6-dial to the resistance equivalent to the check value.
7--12