Target value match ON instruction (F166) Example 1: If the elapsed value (DT90300 and DT90301) for channel 0 matches K10000, output Y7 turns on. Example 2: If the elapsed value (DT90308 and DT90309) for channel 2 matches K20000, output Y6 turns on. Target value match OFF instruction (F167) Example 1: If the elapsed value (DT90304 and DT90305) for channel 1 matches K30000, output Y4 turns off. Example 2: If the elapsed value (DT90312 and DT90313) for channel 3 matches K40000, output Y5 turns off. FP-X Ry type – Elapsed value and target value areas of high-speed counter ch0 to chB High-speed counter Control flag Elapsed value area Target value area Channel No. ch0 R9110 DT90300 to DT90301 DT90302 to DT90303 ch1 R9111 DT90304 to DT90305 DT90304 to DT90307 ch2 R9112 DT90308 to DT90309 DT90310 to DT90311 ch3 R9113 DT90312 to DT90313 DT90314 to DT90315 ch4 R9114 DT90316 to DT90317 DT90318 to DT90319 ch5 R9115 DT90320 to DT90321 DT90322 to DT90323 ch6 R9116 DT90324 to DT90325 DT90326 to DT90327 ch7 R9117 DT90328 to DT90329 DT90330 to DT90331 ch8 R9118 DT90332 to DT90333 DT90334 to DT90335 ch9 R9119 DT90336 to DT90337 DT90338 to DT90339 chA R911A DT90340 to DT90341 DT90342 to DT90343 chB R911B DT90344 to DT90345 DT90346 to DT90347 10-13