Download SMC-50 Solid-State Motor Controller User Manual
Transcript
Appendix B Parameter Information Table 129 - Parameter 52…57 Number Name Units 52 Max. Torque % 53 Cur Limit Level 54 55 Min./Max. [Default] Description 0/300 [250] NA Gives the user ability to configure the maximum torque limit of a torque ramp during a torque start operation. R/W %FLC 50/600 [350] NA The current limit level that is applied for the ramp time selected. R/W Kickstart Time SEC 0.0/2.0 [0.0] NA A boost of current is applied to the motor for this programmed time. R/W Kickstart Level %LRT 0/90 [0] NA Gives the user the ability to adjust the amount of current boost applied to the motor during the kickstart period. R/W — Allows the user to select the operation of Terminal 11, Input 1 on the control module. Disable Disable the input - ignores any assertion to Input 1, Terminal 11. Start Initiates a start as set up by the start parameters at Input 1, Terminal 11 (High). Coast Initiates a coast stop.- no current to motor at Input 1, Terminal 11 (Low). Stop Option Initiates a stop maneuver as set up by the stopping parameters at Input 1 (Low). [Start/Coast] Start/Stop 56 Input 1 — 0/13 [4] Slow Speed — 0/13 [0] if Input 1 = 0- Initiates a stop maneuver as set up by stopping parameters 1- Initiates a start as set up by the start parameters Runs motor in slow speed mode as set up by slow speed parameters (High). OL Select if Input 1 = 0 - Use Motor Overload Class 1 1 - Use Motor Overload Class 2 Fault A fault condition forced if Input 1= 1. Fault NC A fault condition forced if Input 1 = 0. Clear Fault Clear a fault from input 1 Terminal 11 (High). Emerg Run Allow motor to run in emergency run mode if asserted from Input 1, Terminal 11 does not start motor (High). Motor Heater Run motor heating algorithm if asserted from Input 1, Terminal 11 (High). — Allows the user to select the operation of Terminal 10, Option Input 2, on the control module. [Disable] Disable the input - ignores any assertion to Input 2 Terminal 10. Start Initiate a start as set up by the start parameters at Input 2 Terminal 10 (High). Coast Initiates a coast stop.- no current to motor at Input 2 Terminal 10 (Low). Stop Option Initiates a stop maneuver as set up by the stopping parameters at Input 2 (Low). Slow Speed If Input 2= 0 - Stops motor 1- Initiate a start as set up by the start parameters If Input 2 = 0- Initiate a stop maneuver as set up by stopping parameters 1- Initiate a start as set up by the start parameters Runs motor in slow speed mode as set up by slow speed parameters (High). If Input 2= 0 - Use Starting Mode 1 1 - Use Starting Mode 2 OL Select If Input 2 = 0 - User Motor Overload Class 1 1 - Use Motor Overload Class 2 Fault A fault condition is forced if Input 2= 1. Dual Ramp 252 0 - Stops motor 1- Initiates a start as set up by the start parameters 0 - Use starting mode 1 1 - Use starting mode 2 Start/Stop Input 2 if Input 1 = if Input 1 = Dual Ramp Start/Coast 57 Read/Write Access Enum Text Fault NC A fault condition is forced if Input 2 = 0. Clear Fault Clear a fault from Input 2 (High). Emerg Run Allow motor to run in emergency run mode if asserted on Input 2 - does not start motor (High). Motor Heater Run motor heating algorithm if asserted at Input 2 (High). Rockwell Automation Publication 150-UM011B-EN-P - January 2013 R/W R/W