Download Operating Instructions

Transcript
Operating Instructions
for use by heating contractor
Vitotronic 300, Type GW5B
Digital boiler control unit
Vitotronic 300-K, Type MW1B
Weather-compensated digital cascade control unit
VITOTRONIC 300, GW5B
VITOTRONIC 300-K, MW1B
r
r
Vitotronic 300, GW5B
Vitotronic 300-K
Product may not be exactly as shown
IMPORTANT
Certified as a component
part for Viessmann boilers
5693 974 - 01 03/2014
Read and save these instructions
for future reference.
Please file in Service Binder
General
Vitotronic 300 GW5B, 300-K MW1B Operating
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with
the instructions listed below and details printed in this manual can cause product/property damage, severe personal
injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information
found in manual subsections).
For a listing of applicable literature,
please see section entitled “Important
Regulatory and Safety Requirements”.
Warranty
Information contained in this and
related product documentation must
be read and followed. Failure to do
so renders the warranty null and void.
Licensed professional heating contractor
The installation, adjustment, service and maintenance
of this equipment must be performed by a licensed
professional heating contractor.
Please see section entitled
“Important Regulatory and Installation
Requirements”.
2
Advice to owner
Once the installation work is complete, the heating
contractor must familiarize the system operator/
ultimate owner with all equipment, as well as safety
precautions/requirements, shutdown procedure, and
the need for professional service annually before the
heating season begins.
WARNING
Installers must follow local regulations with respect to
installation of carbon monoxide detectors. Follow the
Viessmann maintenance schedule of the boiler contained
in this manual.
Operating and Service Documentation
It is recommended that all product documentation such
as parts lists, operating and service instructions be
handed over to the system user for storage.
Documentation is to be stored near boiler in a readily
accessible location for reference by service personnel.
5693 974 - 01
Product documentation
Read all applicable documentation before commencing
installation. Store documentation near boiler in a
readily accessible location for reference in the future
by service personnel.
General
Vitotronic 300 GW5B, 300-K MW1B Operating
Commissioning
The commissioning and matching of the control unit to
local conditions and building characteristics, as well as
instructing the user in the operation of the system, must
be carried out by your heating contractor. As the user of
new combustion equipment, you may be obliged to notify
your local service technician of the installation [check
local regulations]. Your local service technician will also
inform you [where appropriate] about work he may be
required to perform on your combustion equipment (e.g.
regular checks, cleaning).
Your System is Preset at the Factory
The control units are factory-set for central heating and
DHW heating:
Vitotronic 300-K: “Heating and DHW”
Your heating system is therefore ready for use.
Central heating
Between 06:00 and 22:00 h, the rooms are heated
to 68° F (20° C) “Set room temperature” (standard
heating mode).
Between 22:00 and 06:00 h, the rooms are heated
to 37° F (3° C) “Set red. room temp” (reduced heating
mode, frost protection).
Your heating contractor can make further settings for
you during commissioning. You can change any
settings individually at any time to suit your
requirements (see chapter “Central heating”).
DHW heating
Between 05:30 and 22:00 h, DHW is heated to 122° F
(50° C) “Set DHW temperature”. Any installed DHW
circulation pump is on.
Between 22:00 and 05:30 h, the DHW cylinder
temperature will not be reheated. Any installed DHW
circulation pump is off.
Your heating contractor can make further settings for
you during commissioning. You can change any
settings individually at any time to suit your
requirements (see chapter “DHW heating”).
Frost protection
Your boiler, heating circuits and DHW cylinder are
protected against frost. Wintertime/summertime
changeover
This changeover is automatic.
Time and date
The day and time were set by your heating contractor
during commissioning.
5693 974 - 01
Power failure
All data is saved if there is a power failure.
3
Table of Contents
Vitotronic 300 GW5B, 300-K MW1B Operating
Page
General
Safety, Installation and Warranty Requirements..............2
Commissioning..........................................................3
Your System is Preset at the Factory.............................3
Safety
About these Instructions..............................................6
For your Safety......................................................6
Safety Terminology................................................7
Operation
Main Controls............................................................8
Where to Find the Controls..........................................8
Controls, Vitotronic 300, GW5B...................................9
How to use the Controls, Vitotronic 300, GW5B..........10
Controls, Vitotronic 300-K.........................................11
Menu, Vitotronic 300-K.............................................12
How to use the Controls, Vitotronic 300-K..................13
Central Heating
Starting the Heating System.......................................14
Stopping the Heating System.....................................15
Required Settings (Central Heating).............................16
Selecting a Heating Circuit.........................................16
Setting the Room Temperature...................................17
Setting the Heating Program for Central Heating...........17
Setting the Time Program for Central Heating...............18
Changing the Heating Curve.......................................19
Stopping Central Heating...........................................19
4
Comfort and Energy Saving Functions
Selecting Comfort Function “Party Mode”...................20
Selecting Energy Saving Function “Economy Mode”......20
Selecting Energy Saving Function “Holiday Program”....21
DHW Heating
Required Settings (DHW Heating)................................22
Setting the DHW Temperature....................................22
Setting the Heating Program for DHW Heating..............22
Setting the Time Program for DHW Heating.................23
Stopping DHW Heating..............................................25
Further Adjustments
Selecting the Boiler Sequence.....................................25
Setting the Display Contrast.......................................25
Setting the Display Brightness....................................26
Entering Names for the Heating Circuit........................26
Selecting the Language..............................................27
Setting the Time and Date.........................................27
Setting the Temperature Unit (oC/oF)...........................27
Restoring the Factory Settings....................................28
5693 974 - 01
..
Table of Contents
Vitotronic 300 GW5B, 300-K MW1B Operating
Page
Scanning Options
Scanning Information.................................................29
Scanning Service Messages........................................30
Scanning Fault Messages...........................................31
Burner Fault - Remote Reset....................................32
Emissions Test Mode................................................32
Troubleshooting
Rooms are Too Cold.................................................33
Rooms are Too Hot...................................................33
There is No Hot Water...............................................34
The DHW is Too Hot.................................................34
“Boiler Status Locked” is Displayed at the
Vitotronic 300, GW5B..............................................34
“ ” is Displayed at the Vitotronic 300, GW5B.............35
““ Flashes and “Fault” is Displayed at the
Vitotronic 300, GW5B..............................................35
““ Flashes and “Fault” is Displayed at the
Vitotronic 300-K.......................................................35
“Controls Locked Out”is Displayed at the
Vitotronic 300-K......................................................35
“External Hook-up” is Displayed at the
Vitotronic 300-K.......................................................35
“Central Control” is Displayed at the
Vitotronic 300-K.......................................................35
“External Program” is Displayed at the
Vitotronic 300-K.......................................................35
5693 974 - 01
..
Maintenance
Maintenance............................................................36
Additional Information
Menu Overview, Vitotronic 300, GW5B......................37
Menu Overview, Vitotronic 300-K..............................38
Terminology............................................................41
5
Safety
Vitotronic 300 GW5B, 300-K MW1B Operating
About these Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product
information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.
WARNING
Warnings draw your attention to the presence of
potential hazards or important product information.
Indicates an imminently hazardous situation which,
if not avoided, could result in loss of life, serious injury
or substantial product/property damage.
CAUTION
Cautions draw your attention to the presence of
potential hazards or important product information.
Indicates an imminently hazardous situation which,
if not avoided, may result in minor injury or product/
property damage.
IMPORTANT

Helpful hints for installation, operation or maintenance
which pertain to the product.
This symbol indicates that additional, pertinent
information is to be found.
This symbol indicates that other instructions must
be referenced.
For your Safety
H Flue gas smell
- Deactivate heating equipment.
- Open windows and doors.
- Inform your heating contractor.
H Working on the equipment
All personnel working on the equipment or the heating
system must have the proper qualifications and hold
all necessary licenses. Ensure main power to
equipment, heating system, and all external controls
has been deactivated. Close main gas supply valve.
Take precautions in all instances to avoid accidental
activation of power during service work.
6
H Dangerous conditions
- Deactivate main power immediately.
- Close gas supply valve.
H Maintenance and cleaning
Regular inspection and service by a qualified heating
contractor is important to the performance of the boiler.
Neglected maintenance impacts on warranty; regular
inspection ensures clean, environmentally friendly and
efficient operation. We recommend a maintenance
contract with a qualified heating contractor.
H Technical Data Manual
- Installation Instruction and Service Instructions
- Operating Instructions and User’s Information Manual
Additional applicable literature:
- Accessory manuals
5693 974 - 01
H Operation
Before operating the boiler, make sure you fully
understand its method of operation. Your heating
contractor should always perform the initial start-up
and explain the system. Any warranty is null and void
if these instructions are not followed.
Vitotronic 300 GW5B, 300-K MW1B Operating
For your Safety
Safety
(continued)
CAUTION
Follow these safety instructions closely to avoid the risk
of injury and damage to property.
H Operation
Before operating the boiler, make sure you fully
understand its method of operation. Your heating
contractor should always perform the initial start-up
and explain the system. Any warranty is null and void
if these instructions are not followed.
H Flue gas smell
- Deactivate heating equipment.
- Open windows and doors.
- Inform your heating contractor.
H Working on the equipment
All personnel working on the equipment or the heating
system must have the proper qualifications and hold
all necessary licenses. Ensure main power to
equipment, heating system, and all external controls
has been deactivated. Close main gas supply valve.
Take precautions in all instances to avoid accidental
activation of power during service work.
H Dangerous conditions
- Deactivate main power immediately.
- Close gas supply valve.
H Maintenance and cleaning
Regular inspection and service by a qualified heating
contractor is important to the performance of the boiler.
Neglected maintenance impacts on warranty; regular
inspection ensures clean, environmentally friendly and
efficient operation. We recommend a maintenance
contract with a qualified heating contractor.
H Technical Data Manual
- Installation Instruction and Service Instructions
- Operating Instructions and User’s Information Manual
Additional applicable literature:
- Accessory manuals
If you smell gas
H Don’t smoke! Don’t use naked flames or cause sparks
(e.g. by switching lights or electrical appliances on
and off)
H Open windows and doors
H Close the gas shut-off valve
H Inform your heating engineers/service contractors from
outside the building
H Observe the safety regulations of your gas supply
company (see gas meter) and those of your heating
engineers (see start-up or instruction report).
In emergencies
H Immediately switch off the power supply, e.g. at the
separate fuse or power supply disconnect switch
(unless there is a smell of gas).
H Close the shut-off valves in the oil pipes or close the
gas shut-off valve, whichever applicable.
H Use suitable extinguishers in the event of fire.
Installation of additional components
The installation of additional components which have not
been tested together with the boiler can adversely affect
the function and performance of the boiler.
Our warranty does not cover and we accept no liability
for damage attributable to the installation of such
components.
Boiler room conditions
H Do not use a room in which the air is polluted by
halogenated hydro-carbons (e.g. as contained in
aerosols, paints, solvents and cleaning agents)
H Do not use a room subject to high levels of dust
H Do not use a room subject to permanently high humidity
H The room should be frost-protected
H Max. ambient temperature 95° F (35° C).
H Provide good ventilation and do not close or obstruct
vents (if installed).
This symbol indicates a reference to other instructions
which must be observed.
Safety Terminology
Take note of all symbols and notations intended to draw attention to potential hazards or important product
information. These include ”WARNING” and ”CAUTION”. See below.
WARNING
Indicates an imminently hazardous situation which,
if not avoided, could result in substantial product /
property damage, serious injury or loss of life.
5693 974 - 01
CAUTION
Indicates an imminently hazardous situation which,
if not avoided, may result in minor injury or product /
property damage.
7
Operation
Vitotronic 300 GW5B, 300-K MW1B Operating
The Main Controls
The settings required for operating your heating system
are made on the Vitotronic 300, GW5B of each boiler and
on the Vitotronic 300-K. If the system is equipped with
remote controls, you can also use the remote controls for
some of the settings.
See Operating Instructions for the remote control
The control unit is behind the hinged cover. The hinged
cover is opened by pulling the top gently downwards
towards you.
You must close the hinged cover again after use.
Where to Find the Controls
Each boiler is equipped with its own control unit for
constant temperature operation.
These control units are regulated by a higher weathercompensated cascade control unit.
H Control unit for cascade operation on the boiler:
Vitotronic 300, GW5B
H Higher weather-compensated cascade control unit:
Vitotronic 300-K
You can change all settings for your heating system
centrally at the control unit programming unit.
You may also make such changes at the remote control
units, if your system is equipped with such units.
Remote control operating instructions
8
5693 974 - 01
The settings at the Vitotronic 300, GW5B and Vitotronic
300-K are described in these operating instructions. You
do not need the operating instructions provided with these
control units.
Operation
Vitotronic 300 GW5B, 300-K MW1B Operating
Controls, Vitotronic 300, GW5B
Opening the control unit Vitotronic 300, GW5B
The programming unit is located behind the flap.
To open, pull the flap from the top edge forward.
A Cover flap
Programming unit
5693 974 - 01

Takes you to the previous step in the menu or cancels
a setting that has been started.
Cursor keys
To scroll through the menu or to set values.
OK Confirms your selection or saves the setting.
? No function.
Enables you to call up the menu for settings and
scanning.
9
Operation
Vitotronic 300 GW5B, 300-K MW1B Operating
How to Use the Controls, Vitotronic 300, GW5B
In multi boiler systems, each Vitotronic 300, GW5B
indicates the boiler number on the standard display. The
example shows the boiler water temperature as indicated
by boiler 4.
Note: If a boiler is not operational, the following appears
in the display of the corresponding control unit:
Locked
Disabled
.
Press
This takes you to the menu for settings and scanning.
Symbols
These symbols are not always displayed, but appear
subject to the system version and the operating state.
Flashing displays indicate that modifications can be made.
Menu
S
Information
Further adjustments
Emissions test mode
Heating program
9
Standby mode with frost protection monitoring
The boiler is available to the cascade control unit for
heat production.
Messages
u

Service message
The service interval has expired.
Fault message
Displays
10
Burner in operation
5693 974 - 01
A
Operation
Vitotronic 300 GW5B, 300-K MW1B Operating
Controls, Vitotronic 300-K
Opening the control unit
The programming unit is located behind the flap.
To open, pull the flap from the top edge forward.
A Cover flap
Programming unit
Menu “Help”
You can view a short guide giving an explanation of the
controls and information about heating circuit selection
(see page 16).
Call up the short guide as follows:
H If the screen saver is active (see page 13):
Press OK

akes you to the previous step in the menu or
T
cancels a setting that has been started.
H From anywhere in the menu:
Press
until the standard menu is shown (see the
following chapter).
Press?
Cursor keys
To scroll through the menu or to set values.
OK
Confirms your selection or saves the setting.
?
To call up additional information regarding the
selected menu option.
5693 974 - 01
Calls up the extended menu.
11
Operation
Vitotronic 300 GW5B, 300-K MW1B Operating
Menu, Vitotronic 300-K
There are two control levels available, the “Standard
menu” and the “Extended menu”.
The menu overview can be found on page 39.
Standard menu
Call up the standard menu as follows:
H If the screen saver is active (see page 13)
Press OK.
H From anywhere in the menu:
until the standard menu appears.
Keep pressing
In the standard menu, the number of boilers installed in
the heating system is shown in a specific order (boiler
sequence). You can change the boiler sequence
(see page 25).
The meanings of the icons are as follows:
H Solid white:
The boiler has been enabled by the cascade control unit
and is operating (boiler 3 in this example).
H Solid grey:
The boiler is available for generating heat but has not
been enabled by the cascade control unit (boilers 2 and
4 in this example).
H Solid black and crossed out:
This boiler is not available for heat production (boiler 1
in this example).
Note: 2 minutes after any setting has been made, the
display automatically reverts to the standard menu.
Extended menu
Call up the extended menu as follows:
H If the screen saver is active (see page 13):
Press OK and then
.
H From anywhere in the menu:
Press
.
12
5693 974 - 01
A Dialogue line
Note: Your heating contractor can block the use of the
extended menu. In this case, you can only scan
fault messages.
Operation
Vitotronic 300 GW5B, 300-K MW1B Operating
How to Use the Controls, Vitotronic 300-K
The screen saver will become active if you have not
adjusted any settings on the programming unit for a few
minutes.
The display brightness is reduced.
1.
Press OK. This takes you to the standard menu.
2.
Press
. This takes you to the extended menu
(see page 38). The selected menu option is
highlighted in white.
The dialogue line A (see previous page) then shows
the necessary instructions.
5693 974 - 01
The following diagram shows how to make settings with
different dialogue lines, using the set room temperature
setting as an example.
13
Central Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Starting the Heating System
Vitotronic 300, type GW5B
Controls with cover flap open
Legend
A ON indicator (green)
B Fault indicator (red)
C Emissions test switch (only for service purposes)
D ON/OFF switch
E Fuses
Vitotronic 300-K, type MW1B
Controls with cover flap open
14
1.
Check the heating system pressure.
2.
Check that the ventilation apertures of the installation
room are open and unrestricted.
Note: With open flue operation, the combustion air
is drawn from the installation room.
3.
4.
5.
Open the gas shut-off valve.
Switch ON the power supply, e.g. in breaker panel.
Switch ON the ON/OFF switches at all Vitotronic
300, GW5B and at the Vitotronic 300-K (see chapter
“Controls”). After a short time, the following is
shown on the display:
H Vitotronic 300, GW5B: the standard display
(see page 10)
H Vitotronic 300-K: the standard menu (see page 38)
The green ON indicator illuminates.
Your heating system and, if installed, your remote
control units are now ready to operate.
Note: On every Vitotronic 300, GW5B, “ “ must be
selected, otherwise the Vitotronic 300-K cannot
use the corresponding boiler to produce heat.
5693 974 - 01
Legend
A ON indicator (green)
B Fault indicator (red)
C Emissions test switch (only for service purposes)
D ON/OFF switch
E Fuse
Central Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Stopping the Heating System
With frost protection monitoring
At the Vitotronic 300-K, select the heating program
“Standby mode” for every heating circuit.
H No central heating.
H No DHW heating.
H Frost protection for the heating circuits and the DHW
tank is active.
Extended menu
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Heating program”
5.
“Standby mode” (frost protection monitoring)
Note: The circulation pumps are briefly started every 24
hours to prevent them from seizing up.
Ending the heating program “Standby mode”
Select another heating program.
Stopping individual boilers at the relevant Vitotronic 300,
GW5B
Press the following keys:
1.
From the main screen press
2.
Use
3.
press OK to confirm.
Y.
to select “9“
Without frost protection monitoring (shutdown)
1.
Switch OFF the ON/OFF switches at all Vitotronic
300, GW5B and Vitotronic 300-K (see chapter
“Controls”).
2.
Close the shut-off valves in the oil lines (at the tank
and filter) or close the gas shut-off valve.
3.
Isolate the heating system from its main power
supply, e.g. at a separate MCB/fuse or a mains
isolator.
4.
Where outside temperatures of below 37° F (3° C)
are anticipated, please take suitable measures to
protect the heating system against frost. If necessary,
contact your heating contractor.
Information on a prolonged shutdown
H Circulation pumps may seize up as they are not supplied
with power.
5693 974 - 01
H Vitotronic 300-K:
It may be necessary to reset the date and time
(see page 27).
15
Central Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Required Settings (Central Heating)
Make the settings for central heating at the Vitotronic
300-K.
If you want central heating, check the following points:
H Have you selected the heating circuit?
For settings, see the next chapter.
H Have you set the required room temperature?
For settings, see page 17.
H Have you selected the correct heating program?
For settings, see page 17.
H Have you set the required time program?
For settings, see page 18.
Selecting a Heating Circuit
Extended menu
1.
2.
“Heating”
The heating of all rooms can, if necessary, be split over
several heating circuits.
H In the case of heating systems with several heating
circuits, for all central heating settings, first select the
heating circuit where you want to make a change.
H This selection is not possible in heating systems with
only one heating circuit.
Example:
H “Heating circuit 1” is the heating circuit for the offices
on the ground floor.
3.
for the required heating circuit.
H “Heating circuit 2” is the heating circuit for the offices
on the first floor.
The heating circuits are marked at the factory as “Heating
circuit 1” (HC1), “Heating circuit 2” (HC2) and “Heating
circuit 3” (HC3).
16
5693 974 - 01
If you or your heating contractor have renamed the
heating circuits (e.g. as “Ground floor” etc.), the name
is displayed instead of “Heating circuit ...” (see page 26).
Central Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Setting the Room Temperature
Setting the room temperature for standard heating mode
Factory setting: 68° F (20° C)
Extended menu
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Set room temperature”
5.
Set the required value.
Setting the room temperature for reduced heating mode
(night setback)
Factory setting: 37° F (3° C)
Extended menu
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Set red. room temp”
5.
Set the required value.
The rooms are heated to this temperature:
H Between the time phases for standard heating mode
(see page 18).
H In the holiday program (see page 21).
Setting the Heating Program for Central Heating
Factory setting: “Heating and DHW”
Extended menu
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Heating program”
5.
“Heating and DHW”
H The rooms of the selected heating circuit are heated
in accordance with the room temperature and time
program settings.
5693 974 - 01
H DHW is reheated in accordance with the set DHW
temperature and time program (see chapter “DHW
heating”).
17
Central Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Setting the Time Program for Central Heating
H The time program for central heating is made up of time
phases. One time phase from 6:00 to 22:00 h for every
day of the week is set at the factory.
H You can set the time program individually, to be
the same for every day of the week or different:
You can select up to 4 time phases per day for standard
heating mode. Set the start and end points for each
time phase. Between these time phases, the rooms are
heated with the reduced room temperature (see chapter
“Setting the room temperature for reduced heating
mode”).
H When setting, bear in mind that your heating system
requires some time to heat the rooms to the required
temperature.
H In the extended menu, you can scan the current time
program under “Information” (see chapter “Scanning
information”, “Heating circuit ...” group).
Extended menu:
1.
Example shown:
H Time program for Monday to Friday
(“Mo-Fr”)
H Time phase !:
From 05:00 to 08:30 h
2.
“Heating”
3.
Select the heating circuit if necessary.
4.
“Heating time program”
5.
Select part of the week or a day.
6.
Select the time phase !, ?, § or $.
7.
Set the start and end points for the relevant time
phase.
8.
Press
to exit the menu.
Note: If you want to terminate a time phase setting
process prematurely, keep pressing
until the
required display appears.
H Time phase ?:
From 16:30 to 23:00 h
Example:
You want to set the same time program for every day
except Monday:
Select the period “Monday–Sunday” and set the time
program.
Then select “Monday” and set the time program for this.
Deleting a time phase
18
5693 974 - 01
Set the time for the end point to the same time that was
set for the start point. The display shows the selected
time phase ”- - : - -”.
Central Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Changing the Heating Curve
Your system’s heating characteristics are affected by the
slope and the shift of the selected heating curve.
Further information about the heating curve can be found
under “Terminology” on page 41.
Factory setting:
H Slope: 1.4
H Heating curve shift: 0
H Standard room temperature (set value): 68° F (20º C)
H Reduced room temperature (set value): 37° F (3º C)
Extended menu:
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Heating curve”
5.
“Slope” or “Shift”
Note: Tips on when and how to change the heating
curve slope and shift are displayed by pressing
.
Example:
6.
?
Set the required value.
Change the heating curve slope to 1.5.
A graph clearly shows the change in the heating curve
as soon as you alter the value for slope or shift.
Depending on various outside temperatures (shown on the
horizontal axis), the assigned set supply temperatures for
the heating circuit are highlighted white.
Stopping Central Heating
Extended menu
5693 974 - 01
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Heating program”
5.
“Only DHW” (summer mode, no central heating)
or
“Standby mode” (frost protection monitoring)
19
Comfort and Energy Saving Functions
Vitotronic 300 GW5B, 300-K MW1B Operating
Selecting Comfort Function “Party Mode”
Make the settings for the comfort function at the
Vitotronic 300-K.
With this function, you can change the room temperature
for several hours, e.g. if guests unexpectedly stay longer
in the evening. You do not have to change any existing
control settings. With this function, DHW is reheated to
the selected set temperature.
Extended menu
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Party mode”
5.
Set the room temperature required during party mode.
H The rooms are heated to the required temperature.
H DHW is reheated to the selected set temperature.
H The DHW circulation pump is switched ON (if installed).
Ending party mode
H Automatically when the system switches to standard
heating mode in accordance with the time program.
or
H In the extended menu, set “Party mode” to “OFF”.
Selecting Energy Saving Function “Economy Mode”
Make the settings for the energy saving function at the
Vitotronic 300-K.
To save energy, you can reduce the room temperature
in standard heating mode. For example, if you leave your
home for a few hours.
Extended menu
1.
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Economy mode”
Ending economy mode
H Automatically when the system switches to reduced
heating mode in accordance with the time program.
or
20
5693 974 - 01
H In the extended menu, set “Economy mode” to “OFF”.
Comfort and Energy Saving Functions
Vitotronic 300 GW5B, 300-K MW1B Operating
Selecting Energy Saving Function “Holiday Program”
To save energy, for example over long holidays, you can
activate the “Holiday program”.
Make the settings for this energy saving function at the
Vitotronic 300-K.
Note: The control unit is set up so that the holiday
program applies to all heating circuits. If you
want to make changes, contact your local heating
contractor.
The holiday program has the following effect on the
heating circuits and DHW heating:
H Central heating:
- For heating circuits in the heating program “Heating
and DHW”:
In these heating circuits, the rooms are heated to the
selected reduced room temperature (see page 20).
- For heating circuits in the heating program “Only
DHW”:
No central heating in these heating circuits.
If the heating program “Only DHW” is selected for
all heating circuits, frost protection monitoring is only
enabled for the boiler and DHW tank.
H DHW heating:
DHW heating is switched OFF; frost protection for the
DHW tank is active.
The holiday program starts at 00:00 h the day following
your departure and ends at 00:00 h on the day of your
return. This means the selected time program is active
on the days of departure and return.
Extended menu:
1.
2.
“Heating”
3.
“Holiday program”
4.
Set the required departure and return dates.
Display in the extended menu
In the extended menu, you can scan the selected holiday
program under “Information” (see chapter “Scanning
information”, “Heating circuit ...” group).
Terminating or deleting a holiday program
Extended menu
5693 974 - 01
1.
2.
“Heating”
3.
“Holiday program”
4.
“Delete program”
21
DHW Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Required Settings (DHW Heating)
Make the settings for DHW heating at the Vitotronic 300-K.
If you want DHW heating, check the following points:
H Have you set the required DHW temperature?
For settings, see the next chapter.
H Have you selected the correct heating program?
For settings, see page 22.
H Have you set the required time program?
For settings, see page 23.
Note: The control unit is set up so that DHW heating
applies to all heating circuits. If you want to make
changes, contact your local heating contractor.
Setting the DHW Temperature
Extended menu
1.
2.
“DHW”
3.
“Set DHW temperature”
4.
Set the required value.
Setting the Heating Program for DHW Heating
Extended menu
22
2.
“Heating”
3.
Select the heating circuit, if necessary (see page 16).
4.
“Heating program”
5.
“Heating and DHW” (with central heating)
or
“Only DHW” (summer mode, no central heating)
5693 974 - 01
1.
DHW Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Setting the Time Program for DHW Heating
H The time program for DHW heating is made up of time
phases. One time phase from 5:30 to 22:00 h for every
day of the week is set at the factory.
H Automatic mode is set at the factory for DHW heating.
This means that, in standard heating mode, the DHW
is reheated to the set temperature. To ensure that hot
water is available at the start of standard heating mode,
the time phase for DHW heating begins automatically
half an hour earlier than the time phase for standard
heating mode.
H If you don’t want the automatic mode, you can select
up to 4 individual time phases per day for DHW heating,
which can be the same for every day of the week or
different. Set the start and end points for each time
phase.
H When setting, bear in mind that your heating system
requires some time to heat the DHW to the required
temperature.
H In the “Extended menu”, you can scan the current time
program under “Information” (see chapter “Scanning
information”, “DHW” group).
Extended Menu
1.
2.
“DHW”
3.
“DHW time prog”
4.
“Individual”
5.
Select part of the week or a day.
6.
Select the time phase !, ?, § or $.
7.
Set the start and end points for the relevant time
phase.
Example shown:
8.
Press
H Time program for Monday to Friday
(“Mo-Fr”)
Note: If you want to terminate a time phase setting
process prematurely, keep pressing until the
required display appears.
H Time phase !:
From 04:30 to 06:30 h
H Time phase ?:
From 15:30 to 20:30 h
to exit the menu.
Deleting a time phase
Set the time for the end point to the same time that was
set for the start point. The display shows the selected
time phase ”- - : - -”.
DHW heating once, no longer in the time program
Note: The heating program “Heating and DHW” or “Only
DHW” must be set for at least one system heating
circuit.
Extended menu
5693 974 - 01
Example:
You want to set the same time program for every day
except Monday:
Select the period “Monday–Sunday” and set the time
program.
Then select “Monday” and set the time program for this.
1.
2.
“Heating”
3.
“Party mode”
4.
Disable “Party mode” again with “OFF” to prevent
unintentional central heating with standard room
temperature.
23
DHW Heating
Vitotronic 300 GW5B, 300-K MW1B Operating
Setting the Time Program for DHW Heating
(continued)
Heating system with DHW circulation pump
For further information about the DHW circulation pump,
see chapter “Terminology”.
H Automatic mode is set for the DHW circulation pump
time program. In other words, the DHW circulation
pump operates in parallel to the DHW heating time
program.
H If you don’t want the automatic mode, you can select
up to 4 individual time phases per day for the DHW
circulation pump, which can be the same for every day
of the week or different. Set the start and end points
for each time phase.
H In the “Information” menu, you can scan the current
time program (see chapter “Scanning information”,
“DHW” group).
Note: Activating the DHW circulation pump is only
advisable for those times when DHW is actually
drawn.
Extended menu:
1.
2.
“DHW”
3.
“DHW circ time prog”
4.
“Individual”
5.
Select part of the week or a day.
6.
Select the time phase !, ?, § or $.
7.
Set the start and end points for the relevant time
phase.
8.
Press
to exit the menu.
Note: If you want to terminate a time phase setting
process prematurely, keep pressing
until the
required display appears.
Deleting a time phase
24
5693 974 - 01
Set the time for the end point to the same time that was
set for the start point. The display shows the selected
time phase ”- - : - -”.
DHW Heating/ Further Adjustments
Vitotronic 300 GW5B, 300-K MW1B Operating
Stopping DHW Heating
You do not want to have DHW or heat your rooms.
Extended menu
1.
2.
Select the heating circuit, if necessary (see page 16).
3.
“Heating”
4.
“Heating program”
5.
“Standby mode” (frost protection monitoring)
You do not want DHW, but do want to heat the rooms.
Extended menu
1.
2.
Select the heating circuit, if necessary (see page 16).
3.
“Heating”
4.
“Heating program”
5.
“Heating and DHW”
6.
until the menu is displayed.
7.
“DHW”
8.
“Set DHW temperature”
9.
Select 50° F (10° C).
Selecting the Boiler Sequence
Only for the Vitotronic 300-K.
Subject to the parameters set and internal control
calculations, the control unit offers various boiler
sequences.
You can change the boiler sequence.
Extended menu
1.
2.
“Boiler sequence”
3.
Set the required boiler sequence and confirm with OK.
Setting the Display Contrast
Only for the Vitotronic 300-K.
Extended menu
5693 974 - 01
1.
2.
“Settings”
3.
“Contrast”
4.
Set the required contrast.
25
Further Adjustments
Vitotronic 300 GW5B, 300-K MW1B Operating
Setting the Display Brightness
Only for the Vitotronic 300-K.
If you would like the texts in the menu to be more clearly
legible, change the brightness for “Control”.
You can also alter the screen saver brightness.
Extended menu
1.
2.
“Settings”
3.
“Brightness”
4.
“Control” or “Screen saver”
5.
Set the required brightness.
Entering Names for the Heating Circuits
Only for the Vitotronic 300-K.
You can give heating circuits 1, 2 and 3 (“HC1”, “HC2”
and “HC3”) individual names. The abbreviations “HC1”,
“HC2” and “HC3” will be retained.
Extended menu
1.
2.
“Settings”
3.
“Name for heating circ.”
4.
“Heating circuit 1”, “Heating circuit 2 or “Heating
circuit 3”
5.
“Change?”
6.
You can select the required symbol with
7.
8.
.
takes you to the next character.
Press OK to accept all entered characters at once
and simultaneously exit this menu.
Note: The entered term is deleted with “Reset?”;
“Heating circuit 1” will then be shown again.
Example:
Name for “Heating circuit 1”:
Ground floor
26
5693 974 - 01
The menu shows “Ground floor” for “Heating circuit 1”.
Further Adjustments
Vitotronic 300 GW5B, 300-K MW1B Operating
Selecting the Language
Only for the Vitotronic 300-K.
Extended menu
1.
2.
“Settings”
3.
“Language”
4.
Select the required language.
Setting the Time and Date
Only for the Vitotronic 300-K.
The time and date are factory-set. If your heating system
has been shut down for a long time, it may be necessary
to set the time and date.
Extended menu
1.
2.
“Settings”
3.
“Time/Date”
4.
Set the time and date.
Setting the Temperature Unit (°C/°F)
Vitotronic 300-K
Factory setting: °C
Press the following keys:
1.
2.
scroll to “settings”, select with OK.
3.
scroll to temperature unit, select with OK.
4.
select “°C” or “°F”, select with OK.
5.
to return to main screen.
Vitotronic 300-K
Factory setting: °C
Extended menu
5693 974 - 01
1.
2.
Settings”
3.
“Temperature unit”
4.
Select the temperature unit “°C” or “°F”.
27
Further Adjustments
Vitotronic 300 GW5B, 300-K MW1B Operating
Restoring Factory Settings
Vitotronic 300, GW5B
You can simultaneously reset all changed values to the
factory settings.
Press the following keys:
1.
2.
scroll to “inform”, select with OK.
3.
scroll to “reset data”, select with OK.
4.
select “all data”, select with OK.
5.
select “yes”, select with OK.
6.
to return to main screen.
Factory settings:
H Heating program: “
“
H Temperature unit: °F (°C)
Vitotronic 300-K
You can reset the factory settings of all modified values
for each heating circuit separately.
Extended menu
1.
2.
“Settings”
3.
“Standard setting”
4.
“Heating circuit 1”, “Heating circuit 2” or “Heating
circuit 3”
The following settings and values are reset:
H Set room temperature for standard heating mode
(“Set room temperature”).
H Set room temperature for reduced heating mode
(“Set red. room temp”).
H Heating program (“Heating program”).
H Set DHW temperature (“Set DHW temperature”).
H Time program for central heating (“Heating time
program”).
H Time program for DHW heating (“DHW time prog”).
H Time program for DHW circulation pump
(“DHW circ time prog”).
H Heating curve slope (“Slope”) and shift (“Shift”).
28
5693 974 - 01
Party mode, economy mode and holiday program are
deleted.
Scanning Options
Vitotronic 300 GW5B, 300-K MW1B Operating
Scanning Information
Vitotronic 300, GW5B — scans for every boiler
Subject to the connected components and settings
made, you can scan current temperatures and operating
conditions.
Press the following keys:
1.
and OK together until “service” appears.
2.
until “diagnosis” appears.
3.
until “general” appears.
4.
for the required information and press OK.
5.
to return to main screen.
Note: Information number is displayed, indicating the
current boiler water temperature.
Note: The scan mode terminates automatically after 30 min.
or if you press .
Vitotronic 300-K — scans for the heating system
Subject to the connected components and settings
made, you can scan current temperatures and operating
conditions.
Scanning in conjunction with solar thermal systems
Extended menu
1.
2.
“Solar energy”
The solar energy yield for the past 7 days is displayed
on a graph. The flashing line on the graph indicates that
the current day is not yet over.
Note: Further scanning options, e.g. for the solar circuit
pump hours run, can be found in the extended
menu under “Information” in the “Solar” group.
The extended menu splits the information into groups:
H “General”
H “Heating circuit 1”
H “Heating circuit 2”
H “Heating circuit 3”
H “DHW”
H “Solar”
H “Reset data”
Note: If heating circuits have been given names,
the name is displayed (see chapter
“Entering names for the heating circuits”).
For detailed scanning options for the individual
groups, see chapter “Scanning options in the
extended menu”.
Extended menu
1.
2.
“Information”
3.
Select the group.
4.
Select the required scan.
Resetting data to 0
You can reset the following data:
H In conjunction with a solar thermal system:
Solar energy yield and hours run for the solar circuit
pump and output 22.
H All the above data simultaneously.
Extended menu
5693 974 - 01
1.
2.
“Information”
3.
“Reset data”
29
Scanning Options
Vitotronic 300 GW5B, 300-K MW1B Operating
Scanning Service Messages
Vitotronic 300, GW5B
If your heating system is due for a service, the symbol
“ “ flashes in the display, and “Service” appears.
1.
You can call up the cause of the fault with OK.
2.
Pressing
is due.
3.
If you want to acknowledge the service message,
follow the instructions in the menu.
Contact your local heating contractor.
The service message is transferred to the menu.
? calls up information on the service that
Display in the standard menu
Display in the extended menu
Note: If the service can only be carried out at a later
date, the service message is displayed again the
following Monday.
Calling up an acknowledged service message
Extended menu
1.
2.
“Service”
Vitotronic 300-K
30
5693 974 - 01
No service interval can be set at the Vitotronic 300-K.
No service message is therefore shown.
Scanning Options
Vitotronic 300 GW5B, 300-K MW1B Operating
Scanning Fault Messages
Vitotronic 300, GW5B and 300-K
If any faults have occurred in your heating system, the
symbol ““ flashes on the display, and “Fault” is shown.
The red fault indicator also flashes (see chapter “Starting
the heating system”).
1.
You can call up the cause of the fault with OK.
2.
Pressing ? calls up information on the heating system
functions.
Tips on which measures you can take yourself before
notifying your heating contractor are also displayed.
3.
Make a note of the cause of the fault and the fault
code to the right of it. In this example: “Outside temp
sensor 18” and “Fault A2”
This enables the heating contractor to be better
prepared for the service call and may save additional
travelling costs.
4.
If you want to acknowledge the fault message, follow
the instructions in the menu.
The fault message is transferred to the menu.
Note:
H If you have connected up signalling equipment (e.g.
a buzzer) for fault messages, this is deactivated when
the fault message is acknowledged.
H If the fault can only be rectified at a later date, the fault
message will be displayed again the next day and the
signalling equipment will be switched on again.
Calling up an acknowledged fault message
Extended menu
1.
5693 974 - 01
2.
“Fault”
31
Scanning Options
Vitotronic 300 GW5B, 300-K MW1B Operating
Burner Fault - Remote Reset
Vitotronic 300, GW5B
Note: The following applies to control serial number
7537696 only.
When a combustion controller fault appears, scan the
fault message (see page 28). Resolve the fault condition.
Refer to the Service Instructions.
Once the fault is resolved, continue with the following;
1.
During locking the display will read ‘Combustion
controller locked out’. To continue press OK.
2.
To reset the burner press OK.
3.
The display will return to normal operation once the
burner has been reset.
Emissions Test Mode
Emissions test mode for testing flue gas with boiler water
temperature raised briefly. This test mode should only be
activated by your service technician during the annual
inspection.
Test mode must be activated at the Vitotronic 300,
GW5B of the boiler to be tested and also, for heat
transfer, at the Vitotronic 300-K cascade control unit.
Vitotronic 300, GW5B and Vitotronic 300-K
Move the emissions test switch on both control units
(see chapter “Controls”) to position S.
The following functions are activated:
H Burner is started.
Note: Burner start-up can be delayed, e.g. through fuel
oil preheating.
H All pumps are started.
H Mixing valve remains set to control function
H The temperature controller regulates the boiler water
temperature.
Set the emissions test switch to position a
or
Close the cover flap (see page 9).
32
5693 974 - 01
Ending emissions test mode
Troubleshooting
Vitotronic 300 GW5B, 300-K MW1B Operating
Rooms are Too Cold
Cause
The heating system is switched off
Remedy
H Turn the ON/OFF switches (see chapter “Controls”)
at all control units ON.
H Switch ON the mains isolator, if installed (outside the
boiler room).
Control unit or remote control incorrectly set.
H Check the fuse/MCB in the power distribution board
(main domestic fuse/ MCB), and reset/replace if required.
Check settings and correct if required:
H At every Vitotronic 300: GW5B
“ “ must be set (see page 10).
H At the Vitotronic 300-K:
- “Heating and DHW” must be selected for the heating
circuit (see page 17).
- Room temperature (see page 17).
- Time (see page 27).
- Time program (see page 18).
- Heating curve (see page 19)
H Check the settings at the remote control (if available).
Separate operating instructions
Only when operating with DHW heating:
DHW priority is enabled.
Slab curing function for slab curing drying is active.
(Not used)
No fuel.
“Fault” is displayed at the Vitotronic 300-K, and the red
fault indicator flashes (see chapter “Controls”).
Symbol ““ is displayed by the Vitotronic 300, GW5B.
Wait until the DHW tank has been heated up.
Wait until the slab curing drying time has elapsed.
(Not used)
H With fuel oil or LPG:
Check the fuel reserves and re-order if required.
- With natural gas:
Open the gas shut-off valve or enquire with your gas
supply utility if required.
Scan the type of fault, make a note of the fault code
and acknowledge the message (see page 31).
Contact your local heating contractor if required.
Scan the type of fault, make a note of the fault code
and acknowledge the message (see page 31).
If necessary, notify your heating contractor.
Rooms are Too Hot
Cause
Control unit or remote control incorrectly set.
Remedy
Check settings and correct if required:
- At the Vitotronic 300-K:
- Room temperature (see page 17).
- Time (see page 27).
- Time program (see page 18).
- Heating curve (see page 19).
- Check the settings at the remote control (if available).
Separate operating instructions
5693 974 - 01
“Fault” is displayed at the Vitotronic 300-K, and the red
fault indicator flashes (see chapter “Controls”).
Symbol ““ is displayed by the Vitotronic 300, GW5B.
Emissions test mode is enabled
Scan the type of fault, make a note of the fault code
and acknowledge the message (see page 31).
Contact your local heating contractor if required.
Scan the type of fault, make a note of the fault code
and acknowledge the message (see page 31).
If necessary, notify your heating contractor.
Terminate emissions test mode (see page 32).
33
Troubleshooting
Vitotronic 300 GW5B, 300-K MW1B Operating
There is No Hot Water
Cause
Remedy
The heating system is switched off.
- Turn the ON/OFF switches (see chapter “Controls”)
at all control units ON.
- Switch ON the mains isolator, if installed (outside the
boiler room).
- Check the fuse/MCB in the power distribution board
(main domestic fuse/ MCB), and reset/replace if
required.
Control unit or remote control incorrectly set.
Check settings and correct if required:
- At every Vitotronic 300: GW5B
“ “ must be set (see page 10).
- At the Vitotronic 300-K:
- DHW heating must be enabled (see page 22).
- DHW temperature (see page 22).
- Time (see page 27).
- Time program (see page 23).
- Check the settings at the remote control (if available).
Separate operating instructions
No fuel.
See page 33.
“Fault” is displayed at the Vitotronic 300-K, and the red
fault indicator flashes (see chapter “Controls”).
Scan the type of fault, make a note of the fault code
and acknowledge the message (see page 31).
If necessary, notify your heating contractor.
Symbol ““ is displayed by the Vitotronic 300, GW5B.
Scan the type of fault, make a note of the fault code
and acknowledge the message (see page 31).
If necessary, notify your heating contractor.
The DHW is Too Hot
Cause
Remedy
Control unit incorrectly adjusted.
Check and correct the DHW temperature, if required
(see page 22).
DHW heating is carried out by the solar thermal system.
Check and correct settings, if required, at the solar control
unit.
Separate operating instructions
Emissions test mode is enabled.
Terminate emissions test mode (see page 32).
34
Cause
Remedy
The heating program is enabled or the boiler is shut
down externally.
Set the heating program .
If necessary, notify your heating contractor.
5693 974 - 01
“Boiler Status Locked” is Displayed at the Vitotronic 300, GW5B
Troubleshooting
Vitotronic 300 GW5B, 300-K MW1B Operating
“ ” is Displayed at the Vitotronic 300, GW5B
Cause
Remedy
The time for a service, as specified by your heating
contractor, has arrived.
Proceed as described on page 30.
“” Flashes and “Fault” is Displayed at the Vitotronic 300, GW5B
Cause
Remedy
Heating system fault.
Proceed as described on page 33.
“” Flashes and “Fault” is Displayed at the Vitotronic 300-K
Cause
Remedy
Heating system fault.
Proceed as described on page 33.
“Controls Locked Out” is Displayed at the Vitotronic 300-K
Cause
Remedy
This function is disabled.
Your heating contractor can lift this block.
“External Hook-up” is Displayed at the Vitotronic 300-K
Cause
Remedy
The heating program selected at the control unit was
changed over by an external switching device.
No remedy required.
“Central Control” is Displayed at the Vitotronic 300-K
Cause
Remedy
The settings of the heating and holiday programs will
be adopted from the heating circuit for which “Central
control” has been selected.
-
“External Program” is Displayed at the Vitotronic 300-K
Cause
Remedy
5693 974 - 01
The heating program set at the control unit was changed You can change the heating program.
over by the Vitocom communication interface.
35
Maintenance
Vitotronic 300 GW5B, 300-K MW1B Operating
Maintenance
Cleaning
All equipment can be cleaned with a commercially
available domestic cleaning agent (non-scouring).
You can clean the front of the programming unit with
a microfibre cloth.
Inspection and maintenance
Regular maintenance ensures trouble free, energy
efficient, environmentally responsible and safe heating.
Your heating system must be serviced by an authorised
contractor at least every 2 years. For this, we advise you
to arrange an inspection and maintenance contract with
your local heating contractor.
Boiler
Increasing boiler contamination raises the flue gas
temperature and thereby increases energy losses.
For that reason, all boilers should be cleaned annually.
DHW tank (if installed)
Maintenance and cleaning should be carried out no later
than two years after commissioning and thereafter as
required.
Only a qualified heating contractor should clean the inside
of a DHW tank and the DHW connections.
Refill any water treatment equipment (e.g. a lock
or injection system) in good time, if such equipment
is installed in the cold water supply of the DHW tank.
Observe the manufacturer’s instructions.
Additionally for a Vitocell 100:
We recommend that the correct function of the sacrificial
anode is checked annually by your heating contractor.
The anode function can be checked without interrupting
the system operation.
The heating contractor will check the ground current with
an anode tester.
Safety valve (DHW tank)
The safety valve function should be checked every six
months by venting, either by the system user or the
local heating contractor. The valve seat may become
contaminated (see the valve manufacturer’s instructions).
Potable water filter (if installed)
To maintain high hygienic standards, proceed as follows:
H Replace filter element on non-back flushing filters every
six months (visual inspection every two months).
H On back flushing filters, back flush every two months.
Damaged connecting cables
36
5693 974 - 01
If connecting cables of the appliance or externally installed
electrical accessories are damaged, replace them with
special connecting cables. Replace only with Viessmann
cables. Contact your local heating contractor.
Vitotronic 300 GW5B, 300-K MW1B Operating
Additional Information
Menu Overview Vitotronic 300, GW5B
Standard menu
Information
Settings
General
Reset data
See detailed
scan options
Language DE
Contrast
Brightness
Temperature unit
Extended menu
General
“Boiler temperature”
“Flue gas temp”
“Output 20”
“Output 29”
“Output 52”
Scanning options in the extended menu
Note: Subject to the actual heating system equipment
level, not all of the scans listed here may be
available.
You can scan more details on information marked
with .
“Burner”
“Operating hours”
“Compiled fault”
“Participant no.”
5693 974 - 01
“Input ext. EA1”
37
Additional Information
Vitotronic 300 GW5B, 300-K MW1B Operating
Menu Overview Vitotronic 300-K
Extended menu
Boiler sequence
Heating
DHW
Solar energy
Test mode
Set DHW temperature
DHW time prog
DHW circ time prog
Settings
General
Heating circuit 1 HC1
Heating circuit 2 HC2
Heating circuit 3 HC3
DHW
Solar
Reset data
Time / Date
Language DE
Contrast
Brightness
Temperature unit
Name for heating circ.
Standard menu
Standard setting
38
Detailed scan
options:
see page 39
Party mode
Economy mode
Set room temperature
Set reduced room temp
Heating program
Heating time program
Holiday program
Heating curve
Heating and DHW
Only DHW
Standby mode
5693 974 - 01
Information
Additional Information
Vitotronic 300 GW5B, 300-K MW1B Operating
Menu Overview Vitotronic 300-K
(continued)
Scanning options in the extended menu
Note: Subject to the actual heating system equipment
level, not all of the scans listed here may be
available.
You can scan more details on information marked
with .
General
Heating circuit 1 (HC1)
“Outside temp”
“Heating program”
“Boiler sequence”
- “Slab curing function” (Not used)
“Boiler temperature” Boiler
- “External hook-up”
“Sensor 17 A”
- “Holiday program”
“Sensor 17 B”
- “External program”
“Common supply temp”
- “Party mode”
“Output 20”
- “Economy mode”
“Output 29”
- “Heating and DHW”
“Output 52”
- “only DHW”
“Accessories pump”
- “Standby mode”
“Block 3rd pty dev”
“Central fault mess”
“Operating status:”
“Participant no.”
- “Standard heating mode”
“Input ext. EA1”
- “Reduced mode”
“Time”
- “Standby mode”
“Date”
“Time program”
“Set room temperature”
“Room temperature”
“Set red. room temp”
“Set ext. room temp”
“Set party temp”
“Slope”
“Shift”
“Heating pump”
5693 974 - 01
“Holiday program”
39
Additional Information
Vitotronic 300 GW5B, 300-K MW1B Operating
Menu Overview Vitotronic 300-K (continued)
Heating circuit 2, 3 (HC2, HC3)
DHW
“Heating program”
“DHW time prog”
- “Slab curing function” (Not used)
“DHW circ time prog”
- “External hook-up”
“DHW temperature”
- “Holiday program”
or
- “External program”
In conjunction with 2 DHW tank temperature sensors:
- “Party mode”
“DHW temp top”
- “Economy mode”
“DHW temp bottom”
- “Heating and DHW”
“DHW tank prim pump”
- “only DHW”
“DHW circ pump”
- “Standby mode”
“Operating status:”
- “Standard heating mode”
Solar
- “Reduced mode”
“Collector temp”
- “Standby mode”
“Solar DHW”
“Time program”
“Solar circuit pump” (hours run)
“Set room temperature”
“Solar energy history”
“Room temperature”
“Solar energy”
“Set red. room temp”
“Solar circuit pump” (ON/OFF)
or
“Set ext. room temp”
“Solar circ pump speed”
“Set party temp”
“Heating suppr. DHW”
“Slope”
“SM1 output 22” (ON/OFF)
“Shift”
“SM1 output 22” (hours run)
“Heating pump”
“Sensor 7”
“Mixing valve”
“Sensor 10”
“Supply temperature”
“Heat suppr. heating”
“Return temperature”
40
5693 974 - 01
“Holiday program”
Additional Information
Vitotronic 300 GW5B, 300-K MW1B Operating
Terminology
Setback mode (reduced heating mode)
Heating curve
See “Reduced heating mode”.
Heating curves illustrate the relationship between the
outside temperature, room temperature (set value) and
boiler water or (heating circuit) supply temperature.
The lower the outside temperature, the higher the boiler
water temperature or heating circuit supply temperature.
With the heating program you determine whether you
heat your rooms and DHW, or only heat DHW, or whether
you shut down your heating system with frost protection
monitoring.
You can select the following heating programs:
H “Heating and DHW”
The rooms are heated and DHW is provided (winter
mode).
H “only DHW”
DHW is provided but there is no central heating
(summer mode).
H “Standby mode”
Frost protection for the boiler and the DHW tank is
enabled, no central heating, no DHW heating.
Note: No operating program is available for central
heating without DHW heating. When you want
central heating, hot water is generally also required
(winter mode. If you do want just central heating,
select the heating program “Heating and DHW”
and set the DHW temperature to 50° F (10° C)
(see chapter “Setting the DHW temperature”). This
means that you will not heat DHW unnecessarily,
but frost protection of the DHW tank is ensured.
In order to guarantee sufficient heat and minimum fuel
consumption at any outside temperature, the conditions
of your building and your heating system must be taken
into consideration. The heating curve is set by your
heating contractor for this purpose.
Note: If your heating system includes heating circuits with
mixing valves, then the supply temperature for the
heating circuit without mixing valve is higher by
a selected differential than the supply temperature
for the heating circuits with mixing valve.
Boiler water or supply
temperature
Heating program
Operating status
5693 974 - 01
In the heating program “Heating and DHW”, the operating
status changes from “Standard heating mode” (see page
17) to the operating status “Reduced heating mode”
(see page 20) and vice versa. The times for the operating
status change are defined when the time program is set.
Room
set-point
temperature
Outdoor temperature
The illustrated heating curves apply with the following
settings:
Extension kit for heating circuit with mixing valve
H Heating curve shift = 0
Assembly (accessory) for controlling a heating circuit with
mixing valve.
See “Mixing valve”.
H Standard room temperature (set value) = 68° F (20º C)
41
Additional Information
Terminology
Vitotronic 300 GW5B, 300-K MW1B Operating
(continued)
Example:
For outside temperature 7° F (−14° C):
Legend
A Underfloor heating system, slope 0.2 to 0.8
B Low temperature heating system, slope 0.8 to 1.6
C Heating system with a boiler water temperature in
excess of 167° F (75° C), slope 1.6 to 2.0
Factory settings: Slope = 1.4 and shift = 0
Heating circuit
A heating circuit is a sealed circuit between the boiler and
radiators, in which the heating water circulates.
A heating system may comprise several heating circuits.
For example, one heating circuit for the rooms occupied
by you and one heating circuit for the rooms of a separate
apartment.
Heating circuit pump
Circulation pump for the circulation of the heating water
in the heating circuit.
Actual temperature
Boiler water or
supply temperature
Current temperature at the time of the scan; e.g. actual
DHW temperature.
Mixing valve
Legend
A Changing the slope:
The steepness of the heating curve changes
B Changing the shift:
The heating curves are shifted in parallel in a vertical
direction
42
Night setback
See “Reduced heating mode”.
Standard heating mode
When you are in the house during the day, you can heat
the rooms in standard heating mode. Set the periods
using the time program for central heating. During these
periods, the rooms are heated to the standard room
temperature.
5693 974 - 01
Outside temperature
A mixing valve mixes the water heated in the boiler
with the cooled water returning from the heating circuit.
The water, heated to the right temperature in line with
demand, is pumped to the heating circuit by the heating
circuit pump. The control unit adjusts the heating circuit
supply temperature via the mixing valve to the various
conditions, e.g. different outside temperature.
Additional Information
Vitotronic 300 GW5B, 300-K MW1B Operating
Terminology
(continued)
Standard room temperature
Summer mode
Set the standard room temperature when you are
at home during the day (see chapter “Setting the room
temperature”).
Heating program “Only DHW”.
At warmer times of the year, i.e. when rooms do not
have to be heated, you can disable heating mode.
The boiler remains operational for DHW heating.
Open flue operation
The combustion air is drawn from the room where the
boiler is installed.
DHW tank primary pump
Balanced flue operation
Drinking water filter
The combustion air is drawn from outside the building.
A device that removes solids from the water.
The drinking water filter is installed in the cold water pipe
upstream of the DHW tank or the instantaneous water
heater.
Reduced heating mode
When you are out or during the night, you can heat
the rooms in reduced heating mode (setback mode).
Set the periods using the time program for central heating.
During these periods, the rooms are heated to a reduced
room temperature.
Circulation pump for heating the DHW in the DHW tank.
Weather-compensated mode
When you are out or during the night, set the reduced
room temperature (see chapter “Setting the room
temperature”).
See also “Reduced heating mode”.
In weather-compensated mode, the heating supply
temperature is controlled according to the outside
temperature.
This means that no unnecessary heat is generated in
order to heat the rooms to the set room temperature you
selected.
The outside temperature is captured and transmitted
to the control unit by a sensor fitted outside the building.
Safety valve
DHW circulation pump
Reduced room temperature
A safety device that must be installed by your heating
contractor in the cold water pipe. The safety valve opens
automatically to prevent excess pressure in the
DHW tank.
The DHW circulation pump transports the hot water
around a circuit between the DHW tank and the drawoff points (e.g. hot tap). This makes hot water available
quickly at the draw-off point.
Solar circuit pump
In conjunction with solar thermal systems.
The solar circuit pump delivers the cooled heat transfer
medium from the DHW tank indirect coil to the collectors.
Set temperature
5693 974 - 01
Default temperature that should be reached; e.g. set DHW
temperature.
43
5693 974 - 01
Technical information subject to change without notice.
Printed on environmentally friendly
(recycled and recyclable) paper.
Vitotronic 300 GW5B, 300-K MW1B Operating