SEQUENCE OF OPERATION THERMOSTAT CALLS FOR HEAT LOW WATER CUTOFF CLOSED? WAIT FOR CONDITION TO CHANGE. CLEAR FAULT. RE-TRY OPERATION. NO NO FURTHER ACTION. FAULT DISPLAYED. YES NO FAULT DISPLAYED CIRCULATOR ON NO DISPLAY FAULT HIGH LIMIT CLOSED? NO CIRCULATOR CONTINUES TO RUN HIGH LIMIT OPEN OVER 1 HOUR? YES YES AIR PRESSURE SWITCH OPEN? NO BLOWER OFF. CIRCULATOR CONTINUES TO RUN. DISPLAY FAULT YES BLOWER ON HIGH NO BLOWER RPM CHECK OK? NO CIRCULATOR AND BLOWER CONTINUE TO RUN YES COMPLETE 3 TRIALS TO CHECK RPM? CIRCULATOR CONTINUES TO RUN. BLOWER OFF. DISPLAY FAULT. YES NO AIR PRESSURE SWITCH CLOSED? NO CIRCULATOR AND BLOWER CONTINUE TO RUN YES COMPLETE 3 TRIALS TO CHECK PRESSURE? CIRCULATOR CONTINUES TO RUN. BLOWER OFF. DISPLAY FAULT. YES BLOWER PREPURGE 10 SEC. HOT SURFACE IGNITOR ON IGNITOR WARM UP 10 SEC NO IGNITOR CURRENT CHECK OK? NO CIRCULATOR AND BLOWER CONTINUE TO RUN COMPLETE 3 TRIALS TO CHECK CURRENT? YES CIRCULATOR CONTINUES TO RUN. BLOWER OFF. DISPLAY FAULT. YES GAS VALVE OPEN 4 SEC. IGNITOR OFF NO FLAME DETECTED ? NO CIRCULATOR AND BLOWER CONTINUE TO RUN COMPLETE 3 TRIALS TO DETECT FLAME? YES GAS VALVE REMAINS OPEN. CIRCULATOR CONTINUES TO RUN. BLOWER RUNS AT HIGH OR LOW SPEED DEPENDING ON DIP SWITCH SETTING OR AUTOMATIC HEAT DEMAND. 20 THERMOSTAT SATISFIED. GAS VALVE CLOSED. CIRCULATOR OFF. BLOWER POST PURGE 5 SECONDS. BLOWER OFF. YES CIRCULATOR CONTINUES TO RUN. BLOWER OFF. DISPLAY FAULT. WAIT 1 HOUR. CLEAR FAULT. RE-TRY OPERATION.