DIRECT VENTING WITHOUT VENT TERMINAL Vertical venting configurations All Prodigy 21 boiler models are certified for vertical direct venting utilizing the following configurations. 1. Vent and air intake piping vertically run up through a roof in close proximity. a. For a pitched roof installation, refer to Figure 10. For a flat roof installation, refer to Figure 11. When floor and ceiling passage is necessary, refer to Figure 9. Adhere to all clearances and materials specified in these illustrations. b. The stainless exhaust vent pipe must pass through the roof vertically through a 178 mm (7") min. diameter cutout and appropriate roof flashing. The pipe must exhaust straight up and terminate with a screen terminator. c. The air intake pipe must pass through the roof vertically. The cutout does not require any clearance, but must be sealed with a flashing or other means. The air intake opening must face down by using a 180° elbow with a screen positioned at the opening. The air intake opening must be at least 305 mm (1 foot) below the vent opening. Figure 9. Floor and ceiling venting passage All items shown below are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT. 8 Figure 10. Vent and air intake run through a pitched roof Figure 11. Vent and air intake run through a flat roof