Installation UM353-1 8.4.13 Wiring to a Model 363 VIEWPAC Recorder Figure 8-25 shows the wiring needed to connect a Model 363 analog input to a Moore 353 analog input. As shown, a 1-5 Vdc transmitter input to the Moore 353 is also routed the recorder’s Analog Input 1. Model 363 VIEWPAC Recorder Terminals Model 353A or 354/354N Controller Terminals External Power 120/240 Vac 25W 47-63 Hz Hot H H Neutral N N Earth Ground G G 5 A5 Recorder Analog Input 1, A6 See note 2 26 Vdc Analog Input, + e.g. Model 340 or SITRANS P DSIII, _ 2-Wire Transmitter, 4-20 mA Output 1-5 Vdc 250 20 AIN1 18 Station Common _ Analog Input, e.g. Model 340 or SITRANS P DSIII, + 2-Wire Transmitter, 4-20 mA Output A7 Recorder Analog Input 2, See note 2 A8 X03109S3 _ + Power Supply Common Ground Bus Earth Ground Recorder Power Input and Ground, See note 3 Notes: 1. See UM353-1, UM354-1, or UM354N-1, Table 8.1 for AIN2, 3, and 4 terminals. 2. Recorder inputs are isolated 1-5 Vdc, Refer to UM363-1 for other Recorder analog inputs. 3. Refer to UM363-1 for power requirements and detailed wiring and grounding information. FIGURE 8-25 Moore 353 To Model 363 VIEWPAC Analog Input Wiring 8.4.14 Power Wiring Basic connections for AC and DC power input are shown in Figure 8-26. Wiring guidelines are given in Section 8.4.2. Model 353A Rear Terminals X03106S0 H Neutral N Earth Ground G H AC To DC Power Supply on MPU Board =Terminal on rear of case. External Power 24 Vdc 25W (+) H (-) N Earth Ground DC To DC Power Supply on MPU Board G Controller Circuitry Hot Controller Circuitry External Power 120/240 Vac 25W 47-63 Hz Model 353D Rear Terminals G = Green screw at top center of rear terminal area. FIGURE 8-26 Controller Power Wiring 8-24 March 2003