Download Moore 353 USER'S MANUAL
Transcript
Factory Configured Options UM353-1 4.3 FCO103 - External Set Controller with Tracking Local Setpoint Factory Configured Option FCO103 provides a single loop controller with external setpoint configured in Loop01. A block diagram of the loop configuration is shown below along with any changes to the default parameter values of the configured blocks. This configuration provides setpoint tracking. If a fixed setpoint is desired, the TC input to the SETPT function block can be set to UNCONFIG. If the loop tag ‘LOOP01’ is changed, all configured references will automatically be changed to the new tag. S External Setpoint 0.00-100.00 PRCT AIN2 DOUT1 X A1 P D O1 A2 ALARM A3 QS S A4 DOUT2 A NC NO MD C E SETPT O1 ST TV TC OR01 B PB2SW PS O1 I SR S SE E/I O1 SI IS IO ES LU LD Process 0.00-100.00 PRCT AIN1 O1 P S QS P F A I PID O1 A O1 S AE TV AS D AW TC NA QS EM A/M AOUT1 MS ES Valve SS V LOOP01 SETPT - Setpoint Function Block RG PTR - Range Pointer ------ Loop01.AIN1.OR INPUT TV - Input TV --------- Loop01.AIN1.O1 INPUT TC - Input TC --------- Loop01.OR01.O1 ESN - Exec. Seq. No.----------- 10 PB2SW - PB2 Switch Function Block INPUT MD - Input MD ------- Loop01.E/I.SE ESN - Exec. Seq. No. ---------- 5 ALARM - Alarm Function Block RG PTR - Range Pointer ------- Loop01.AIN1.OR INPUT P - Input P -------------- Loop01.AIN1.O1 INPUT D - Input D ------------- Loop01.E/I.O1 ESN - Exec. Seq. No. ---------- 20 PID - PID Controller Function Block RG PTR - Range Pointer ----------- Loop01.AIN1.OR INPUT P - Input P ------------------ Loop01.AIN1.O1 INPUT S - Input S ------------------ Loop01.E/I.O1 INPUT F - Input F ------------------ Loop01.A/M.O1 INPUT A - Input A ----------------- Loop01.A/M.AS INPUT I - Input I ------------------- Loop01.E/I.ES ESN - Exec. Seq. No.--------------- 25 4-4 E/I - Ext/Int Transfer Switch Function Block INPUT ST - Input ST -------------- Loop01.PB2SW.PS INPUT E - Input E ------------------ Loop01.AIN2.O1 INPUT I - Input I ------------------- Loop01.SETPT.O1 ESN - Exec. Seq. No. -------------- 15 A/M - Auto/Manual Function Block RG PTR - Range Pointer ---------- Loop01.PID.OR INPUT A - Input A ----------------- Loop01.PID.O1 ESN - Exec. Seq. No. -------------- 30 OR01 - OR Function Block INPUT A - Input A ----------------- Loop01.E/I.ES INPUT B - Input B ----------------- Loop01.A/M.MS ESN - Exec. Seq. No. -------------- 35 AOUT1 - Analog Output 1 Function Block RG PTR - Range Pointer ------------ Loop01.PID.OR INPUT S - Input S ------------------- Loop01.A/M.O1 March 2003