MORLEY-IAS
Dimension Series
[U0 Disable/Enable]
1:Sounders
2:Fault Relays
•
3:Others
It is possible to enable or disable:
1.
ALL Sounder Type Outputs.
2.
ALL Fault Relay Type Outputs.
3.
ALL Other Relay and Control Type Outputs
•
Press ‘1’, ‘2’ or ‘3’ are as required. The display then shows the following if the outputs are currently
enabled.
Disable ALL Sounder Outputs
Press 9 to Confirm
X:Cancel
Disable ALL Fault Relay Outputs
Press 9 to Confirm
X:Cancel
Disable ALL Relay and CTL Outputs
Press 9 to Confirm
•
X:Cancel
The display shows the following if the outputs are currently disabled.
Enable ALL Sounder Outputs
Press 9 to Confirm
X:Cancel
Enable ALL Fault Relay Outputs
Press 9 to Confirm
X:Cancel
Enable ALL Relay and CTL Outputs
Press 9 to Confirm
X:Cancel
•
Press the ‘9’ key to confirm the enable / disable action and return to the enable / disable outputs
menu.
•
Press ‘X’ to return to the enable / disable outputs menu without making a change.
5.3.5.5
Disable / Enable Detection Mode
EN54-2 7.11.2
EN54
Delays to
Outputs.
9
•
It is possible to manually override (turn on / off) detection mode
delays.
•
Detection Modes can be Stage 1 / Stage 2 Investigation Mode (see section 6) or Sensitivity Mode
(Detector sensitivity is adjusted at certain times of the day) or Alarm Verification Mode (The signals
from smoke detectors must be verified after a programmed period of time before a fire alarm is
raised). All of these modes are useful in reducing false alarms and will have been programmed by the
commissioning engineer to suit the requirements / use of the building.
•
The normal activation of these modes is based on a ‘7-day’ clock timer to be active at specific times
of day or night. The clock timers can be overridden to turn on / off the operation manually. Starting
the detection mode will activate the function until it is next scheduled to turn off automatically. Ending
Page 28 of 44
Document No. 996-148, Revision: 02
User Manual