Transcript
RST_FACTORY 5 Writing True (1) to this coil will force all settings to Factory defaults. Always read as False (0). After setting this coil to true, the device will automatically reset so the new settings will take effect. 4 Example MODBUS Request: Read GWC MODBUS Command: read coils 1-5 (OR RAW 0-4) DEFAULT MODBUS SETTINGS: Address: 95 (0x5F) MODBUS ASCII Poll Gateway Coils: “:63010000000595<CR><LF>“ MODBUS RTU Poll Gateway Coils: 0x63 01 00 00 00 05 75 8A • 63 is address • 01 is function code (read coils) • 00 is address high • 00 is address low • 00 is coil count high • 05 is coil count low • 758A is CRC for RTU protocols 95<CR><LF> is the check sum and end-of-line for ASCII protocols - 21 -