8 FIXED BUFFER COMMUNICATION (WITH THE NO PROCEDURE CONTROL METHOD) MELSEC-Q 8.5.2 Receiving by simultaneous broadcasting Data is received through simultaneous broadcasting, by setting FFFFFFFFH for the IP address of an external device that is to send data to the Ethernet module, and FFFFH for the port No., then performing the open processing. (1) Setting screen This section explains the "Open settings" for receiving by simultaneous broadcasting. • Connection No. 16 is used. • The Ethernet module Port No. is 0801H. 8 - 13 (a) Protocol Select "UDP/IP". (b) Open system Setting is not required. (c) Fixed buffer Select "Receive". (d) Fixed buffer communication Select "No procedure". (e) Pairing open Select "No pairs". (f) Existence confirmation Select "No confirm". 8 - 13