6 Programming Features
When operating with a frequency larger than 60/50 Hz, change only the
Max. Output Frequency (n011).
Constant torque
Constant output or
variable output
n012
=200 V
Base point
n013
=60 or 50 Hz
n011
=90 Hz
„ Switching LOCAL/REMOTE Mode
The following functions can be selected by switching LOCAL or
REMOTE mode. To select the Run/Stop Command or frequency reference, change the mode in advance depending on the following applications.
• LOCAL mode: Enables the Digital Operator for Run/Stop Commands and FWD/REV Run Commands. The frequency reference can be set using the potentiometer
or
.
• REMOTE mode: Enables Run Command Selection (n003).
The frequency reference can be set using the Frequency Reference Selection (n004).