Download VARISPEED V7 USER'S MANUAL
Transcript
6 Programming Features When operating with a frequency larger than 60/50 Hz, change only the Max. Output Frequency (n011). Constant torque Constant output or variable output n012 =200 V Base point n013 =60 or 50 Hz n011 =90 Hz Switching LOCAL/REMOTE Mode The following functions can be selected by switching LOCAL or REMOTE mode. To select the Run/Stop Command or frequency reference, change the mode in advance depending on the following applications. • LOCAL mode: Enables the Digital Operator for Run/Stop Commands and FWD/REV Run Commands. The frequency reference can be set using the potentiometer or . • REMOTE mode: Enables Run Command Selection (n003). The frequency reference can be set using the Frequency Reference Selection (n004). 61