Download User Manual
Transcript
SUN2000 (8KTL-28KTL) User Manual 5 Electrical Connections 5.2 Connecting AC Output Power Cables Connect the SUN2000 to the AC power distribution frame (PDF) or power grid over AC input power cables. Prerequisites An independent there-phase circuit breaker for each inverter must be installed at the output side to ensure that the inverter can be securely disconnected. See 10 Technical Specifications to select the specifications of breaker. It is not allowed for several inverters to use the same circuit breaker. It is not allowed to connect loads between inverter and circuit breaker. Context Huawei recommends a soft cable for ease of installation. The outer diameter of the conductor should be less than or equal to 4.2 mm. Table 5-1 lists the specifications. Table 5-1 Recommended AC output power cable specifications Inverter Model Range SUN2000 -8KTL SUN2000 -10KTL Cross-sectional Area (mm2) Cable Type SUN2000 -12KTL Recommended Range Value 4-core 4-core outdoor outdoor cable (3+N) cable (3+N) Recommended Range Value 4–10 4 (12AWG) (12AWG– 8AWG) 5-core outdoor cable (3+N+PE) SUN2000 -15KTL 6–10 6 (10AWG) (10AWG– 8AWG) SUN2000 -17KTL SUN2000 -20KTL SUN2000 -23KTL SUN2000 -24.5KTL 3-core outdoor Issue 07 (2014-07-30) External Cable Diameter (mm) 3-core outdoor cable Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd. 11–20 Recommended Value 15 NOTE When the outer cable diameter ranges from 11 mm to 13 mm, add cable clamps. When the outer cable diameter ranges from 16 mm to 20 mm, strip a seal ring from the cable sealing cover interior. When the outer diameter of an armored cable exceeds 20 mm, strip the jacket and armored layer and take waterproof and 45