Download it

Transcript
FX3U Series Programmable Controllers
4 Specifications, External Dimensions and Terminal Layout (Main Units)
User’s Manual - Hardware Edition
1
Product life of relay contacts
The standard life of the contact used for conductive AC loads, such as contactors and solenoid valves, is
500,000 times at 20 VA.
The following table shows the approximate life of the relay based on the results of our life test.
Test condition: 1 sec. ON / 1 sec.OFF
Example of applicable loads
(Magnetic switch manufactured by our company)
0.2 A / 100V AC
20 VA
0.1 A / 200V AC
3,000,000 times
S-K10 to S-K95
0.35 A / 100V AC
0.17 A / 200V AC
1,000,000 times
S-K100 to S-K150
200,000 times
S-K180,S-K400
0.8 A / 100V AC
80 VA
0.4 A / 200V AC
3
Product
Introduction
35 VA
If rush overcurrent is shut off even under the above condition, the life of the relay contact is considerably
decreased.
Transistor output (sink type)
The output numbers in the table indicate the main unit terminal numbers. "Y010 or more" means the numbers
from Y010 to the largest number that the main unit has.
(The output numbers of FX3U-16MT/ S are Y000 to Y007.)
FX3U-16MT/ S FX3U-32MT/ S FX3U-48MT/ S FX3U-64MT/ S FX3U-80MT/ S FX3U-128MT/ES
8 points
Connecting type
Fixed terminal
block
(M3 screw)
16 points
Output type/form
24 points
32 points
40 points
64 points
6
Removable terminal block (M3 screw)
System
Configuration
Number of output
points
Transistor/sink output
External power
supply
5 to 30V DC
Installation
0.1 mA or less/30V DC
ON voltage
1.5 V or less
−
Min. load
OFF→ON
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
ON→OFF
Y000 to Y002:5 µs or less/10 mA or more (5 to 24V DC)
Y003 or more:0.2 ms or less/200 mA or more (at 24V DC)
Circuit insulation
Photocoupler insulation
Display of output
operation
LED on panel lights when photocoupler is driven.
9
Preparation and
Power Supply
Wiring
Response
time
8
12W/24V DC
Open circuit leakage
current
7
Input/Output
Nos., Unit Nos.
0.5A / point
The total load current of resistance loads per common terminal should be the following value.
→ For details on the common terminal for each model,
Resistance
refer to the terminal block layout.
load
• 1 output point/common terminal: 0.5 A or less
Max. load
• 4 output points/common terminal: 0.8 A or less
• 8 output points/common terminal: 1.6 A or less
Inductive
load
5
Version and
Peripheral
Devices
Item
Transistor output (sink) specifications
4
Specifications
4.4.3
2
Features and
Part Names
Contact life
Load capacity
Introduction
4.4.2
4.4 Output Specifications
10
Input Wiring
53