Section Errors and Alarm Troubleshooting 7-1 Errors that occur during initial processing (at CPU Unit power ON or restart of the Loop Control Unit) LED RUN ERH ERC Out Lit Out Item Unit number setting error State 1) The same unit All functions number has been stopped specified twice or more on the same CPU Unit. 2) The unit number is not registered to CPU Unit I/O table. 3) Failed to recognize the CPU Unit Error code (stored as Remedy error log data) None 1) Set the correct unit number, and turn the power back ON again. 0006 detailed 2) Prepare an I/O table. code: 0800 None 4) Error occurred during initial processing on CPU Unit. Initial Failed to recognize the All functions recognition CPU Unit stopped error 000F All functions stopped None All functions stopped None Out Lit Lit Out Out Lit Unit error Out Out Out Power supply failure Lit Function block database error (not (not related) related) Cause Hardware malfunction such as memory malfunction was detected during the selfdiagnostic test. 1) The correct internal power is not being supplied to the Loop Control Unit. None 3) Replace the Loop Control Unit if ERH lights even if mounted on a different CPU Unit. 4) Refer to the CPU Unit Operation Manual. Replace the Loop Control Unit if ERH/ERC light even if mounted on a different CPU Unit. Replace the Loop Control Unit if ERC lights even if mounted on a different CPU Unit. 1) Check the power voltage, and supply the correct power. Or, check the total current consumption of the PC. 2) The unit is not 2) Firmly fix the Loop properly fixed to the Control Unit on the Backplane. Backplane. 3) The unit is 3) Replace the Loop malfunctioning. Control Unit if LED goes off even if mounted on a different CPU Unit. 1) Drop in internal All functions 0331 1) Check the battery battery power voltage stopped Detailed code: connection. If the or battery not Running Block connection is normal, mounted (Only when stopped address. replace the battery. DIP switch pin 2 is FFFF Then execute OFF) indicates that initialization using CXthe entire Process Tool. 2) Data corruption In the case of database is in 2) Set the data again to caused by noise only a partial error. the function block in error, running question using CXis stopped Process Tool. only at the function block in question. 193