Download Blast Chiller
Transcript
Control in: 6.c Time remaining before next unit control h Change language Show screen when starting 6.d Change the language of the user interface 6.d Change language in: 6.d Enable display of the change language screen at start-up Delay time within which the change of language is accepted without modifications Unit of measure 6.d Change temperature unit of measure 30000 - 0 to 30000 English, French, Italian, German, Spanish - NO/YES YES s 0 to 9999 60 - °C/ °F °C English Date setting 6.d Change the date settings - dd/mm/yy, mm/dd/yy dd/mm/yy Enable buzzer 6.d Enable the buzzer - N/ Y Y New PSW 6.d Change the user password - 0 to 9999 1234 1234, 1234 Maintenance - main menu Enter password 7.a Maintenance or manufacturer password - 0 to 9999 Type of board 7.a Type of hardware - pCO , pCO Boot 7.a Boot version - … - Bios 7.a Bios version - - 1 3 xs BMS protoc. 7.b.a, ba02 Protocol used on the BMS port - … Carel, ModBus, LON, Carel RS232, printer BMS address 7.b.a, ba02 Address for the supervisory system - 1 to 200 BMS speed 7.b.a Communication speed of the BMS serial port bps Field Bus protocol 7.b.a Protocol used for the Field Bus serial port Field Bus speed Compressor op. hour threshold Reset compressor op. hours Compressor 2 op. hour threshold Reset compressor 2op. hours Evap. fan op. hour threshold Reset evap. fan op. hours Cond. fan op. hour threshold Cond evap. fan op. hours UV light op. hour threshold 7.b.a Select the communication speed of the Field Bus serial port - printer - 1200, 2400, 4800, 9600, 19200 19200 Carel, ModBus, Carel RS232, printer Carel bps 1200, 2400, 4800, 9600, 19200 19200 7.b.b, bb01 Compressor op. hour threshold h 0 to 30000 30000 7.b.b, bb01 Reset compressor op. hours - NO/YES NO 7.b.b, bb02 Second compressor op. hour threshold h 0 to 30000 30000 7.b.b, bb02 Reset second compressor op. hours - NO/YES NO 7.b.b, bb03 Evaporator fan op. hour threshold h 0 to 30000 30000 7.b.b, bb03 Reset evaporator fan op. hours - NO/YES NO 7.b.b, bb04 Condenser fan op. hour threshold h 0 to 30000 30000 7.b.b, bb04 Reset condenser fan op. hours - NO/YES NO 30000 7.b.b, bb05 UV light op. hour threshold h 0 to 30000 Reset UV light op. hours 7.b.b, bb05 Reset UV light op. hours - NO/YES NO Unit op. hour threshold 7.b.b, bb06 Unit op. hour threshold h 0 to 30000 30000 Reset unit op. hours 7.b.b, bb06 Reset unit op. hours - NO/YES NO Probe B1 offset 7.b.c, bc01 Offset in the reading of probe B1 °C -9.9 to +9.9 0.0 … … … 7.b.c, bc03 Offset in the reading of probe B5 °C -9.9 to +9.9 0.0 7.b.d, bd01 Blast chiller/freezer temperature diff. °C 2.0 compressor … Probe B5 offset Blast chiller/freezer temperature diff. Device connected to digital output 1 Operating mode Digital output 1 in manual operating mode ... Device connected to digital output 8 Operating mode Digital output 8 in manual operating mode Device connected to analogue output 1 Operating mode of analogue output 1 7.c … 7.c, c01 Device connected to digital output 1 - 0.0 to 90.0 See Chap. 9 CONFIGURATIONS 7.c, c01 Operating mode of digital output 1 - Auto, Manual Auto 7.c, c01 Digital output 1 in manual operating mode - On/ Off Off … … 7.c, c08 Device connected to digital output 8 - … See Chap. 9 CONFIGURATIONS 7.c, c08 Operating mode of digital output 8 - Auto, Manual Auto 7.c, c08 Digital output 8 in manual operating mode - Off 7.c, c09 Device connected to analogue output 1 - On/ Off See Chap. 9 CONFIGURATIONS 7.c, c09 Operating mode of analogue output 1 - Auto, Manual Auto +030220851- rel. 1.3 - 09.12.2008 … 36 defrost Steril.