Control in:
6.c
Time remaining before next unit control
h
Change language
Show screen when
starting
6.d
Change the language of the user interface
6.d
Change language in:
6.d
Enable display of the change language screen at start-up
Delay time within which the change of language is accepted without
modifications
Unit of measure
6.d
Change temperature unit of measure
30000
-
0 to 30000
English, French,
Italian,
German,
Spanish
-
NO/YES
YES
s
0 to 9999
60
-
°C/ °F
°C
English
Date setting
6.d
Change the date settings
-
dd/mm/yy, mm/dd/yy
dd/mm/yy
Enable buzzer
6.d
Enable the buzzer
-
N/ Y
Y
New PSW
6.d
Change the user password
-
0 to 9999
1234
1234,
1234
Maintenance -
main menu
Enter password
7.a
Maintenance or manufacturer password
-
0 to 9999
Type of board
7.a
Type of hardware
-
pCO , pCO
Boot
7.a
Boot version
-
…
-
Bios
7.a
Bios version
-
-
1
3
xs
BMS protoc.
7.b.a, ba02 Protocol used on the BMS port
-
…
Carel, ModBus, LON, Carel
RS232, printer
BMS address
7.b.a, ba02 Address for the supervisory system
-
1 to 200
BMS speed
7.b.a
Communication speed of the BMS serial port
bps
Field Bus protocol
7.b.a
Protocol used for the Field Bus serial port
Field Bus speed
Compressor op. hour
threshold
Reset compressor op.
hours
Compressor 2 op. hour
threshold
Reset compressor 2op.
hours
Evap. fan op. hour
threshold
Reset evap. fan op.
hours
Cond. fan op. hour
threshold
Cond evap. fan op.
hours
UV light op. hour
threshold
7.b.a
Select the communication speed of the Field Bus serial port
-
printer
-
1200, 2400, 4800, 9600, 19200 19200
Carel, ModBus, Carel RS232,
printer
Carel
bps
1200, 2400, 4800, 9600, 19200 19200
7.b.b, bb01 Compressor op. hour threshold
h
0 to 30000
30000
7.b.b, bb01 Reset compressor op. hours
-
NO/YES
NO
7.b.b, bb02 Second compressor op. hour threshold
h
0 to 30000
30000
7.b.b, bb02 Reset second compressor op. hours
-
NO/YES
NO
7.b.b, bb03 Evaporator fan op. hour threshold
h
0 to 30000
30000
7.b.b, bb03 Reset evaporator fan op. hours
-
NO/YES
NO
7.b.b, bb04 Condenser fan op. hour threshold
h
0 to 30000
30000
7.b.b, bb04 Reset condenser fan op. hours
-
NO/YES
NO
30000
7.b.b, bb05 UV light op. hour threshold
h
0 to 30000
Reset UV light op. hours
7.b.b, bb05 Reset UV light op. hours
-
NO/YES
NO
Unit op. hour threshold
7.b.b, bb06 Unit op. hour threshold
h
0 to 30000
30000
Reset unit op. hours
7.b.b, bb06 Reset unit op. hours
-
NO/YES
NO
Probe B1 offset
7.b.c, bc01 Offset in the reading of probe B1
°C
-9.9 to +9.9
0.0
…
…
…
7.b.c, bc03 Offset in the reading of probe B5
°C
-9.9 to +9.9
0.0
7.b.d, bd01 Blast chiller/freezer temperature diff.
°C
2.0
compressor
…
Probe B5 offset
Blast chiller/freezer
temperature diff.
Device connected to
digital output 1
Operating mode
Digital output 1 in
manual operating mode
...
Device connected to
digital output 8
Operating mode
Digital output 8 in
manual operating mode
Device connected to
analogue output 1
Operating mode of
analogue output 1
7.c
…
7.c, c01
Device connected to digital output 1
-
0.0 to 90.0
See Chap. 9
CONFIGURATIONS
7.c, c01
Operating mode of digital output 1
-
Auto, Manual
Auto
7.c, c01
Digital output 1 in manual operating mode
-
On/ Off
Off
…
…
7.c, c08
Device connected to digital output 8
-
…
See Chap. 9
CONFIGURATIONS
7.c, c08
Operating mode of digital output 8
-
Auto, Manual
Auto
7.c, c08
Digital output 8 in manual operating mode
-
Off
7.c, c09
Device connected to analogue output 1
-
On/ Off
See Chap. 9
CONFIGURATIONS
7.c, c09
Operating mode of analogue output 1
-
Auto, Manual
Auto
+030220851- rel. 1.3 - 09.12.2008
…
36
defrost
Steril.