4 Domestic hot water control
The C203 tries to keep the temperature of domestic hot water at
the designated setting value. This ensures that the temperature
of water from the shower always remains constant. Because of
danger of bacteria, it is recommended that the domestic hot water
temperature is not permanently set below +55°C.
Main mene
H1 Control circuit
>
DH Domestic hot water control
>
H2 Control circuit
>
Alarms
>
4.1 Setting values
DH Domestic hot water control -> Setting values
D H D o m e s t i c h o t wa t e r c o n t r o l
Setting values
>
Control mode
Automatic >
Measurements
>
HW S e t t i n g va l u e s
Domestic hot water etting value
58.0 °C
Anticipation control
In use
Domestic hot water control
Setting name
In use
>
>
Range
Domestic hot water setting value
Factory
setting
58.0 °C
Explanation
20...90 °C
Domestic hot water temperature setting.
Anticipation control
In use
In use/
Not in use
Anticipation speeds up regulation when water consumption
changes by using measurement information from the circulation water sensor. The regulator recognises the sensor and
automatically starts to use anticipation when the sensor is
turned on. You can also stop using anticipation.
4.2 Control mode
DH Domestic hot water control -> Control mode
Automatic mode is normally used in regulating domestic hot waD o m e s t i c h o t wa t e r c o n t r o l
ter. Here you can switch from automatic to manual mode and move
Setting values
>
Control mode
Automatic >
the vent into the desired position. You can use manual mode for
Measurements
>
example when a sensor malfunctions.
Control mode
Automatic
Manual
Control mode
Explanation
Automatic
Manual
C203 maintains the temperature of domestic hot water at the setting value
set by the user.
LV K ä y t t ö v e d e n s ä ä t ö
Asetusarvot
Ohjaustapa
LV Käsiajoasento
Mittaukset
Manual mechanical
>
Käsiajo >
The position of the desired vent is set with the setting value ”HW Manual position.”
0% >
>
In mechanical manual mode the valve’s position is set from the actuator. To
prevent the regulator from changing the position of the valve, the actuator’s
power input must be disconnected.
4.3 Measurements
DH Domestic hot water control -> Measurements
The ”Measurements” menu under the circuit shows the measurements related to the circuit.
All measurements linked to the regulator can be found in the Measurements menu at the root level (see page
7).