Download USER MANUAL
Transcript
4 Domestic hot water control The C203 tries to keep the temperature of domestic hot water at the designated setting value. This ensures that the temperature of water from the shower always remains constant. Because of danger of bacteria, it is recommended that the domestic hot water temperature is not permanently set below +55°C. Main mene H1 Control circuit > DH Domestic hot water control > H2 Control circuit > Alarms > 4.1 Setting values DH Domestic hot water control -> Setting values D H D o m e s t i c h o t wa t e r c o n t r o l Setting values > Control mode Automatic > Measurements > HW S e t t i n g va l u e s Domestic hot water etting value 58.0 °C Anticipation control In use Domestic hot water control Setting name In use > > Range Domestic hot water setting value Factory setting 58.0 °C Explanation 20...90 °C Domestic hot water temperature setting. Anticipation control In use In use/ Not in use Anticipation speeds up regulation when water consumption changes by using measurement information from the circulation water sensor. The regulator recognises the sensor and automatically starts to use anticipation when the sensor is turned on. You can also stop using anticipation. 4.2 Control mode DH Domestic hot water control -> Control mode Automatic mode is normally used in regulating domestic hot waD o m e s t i c h o t wa t e r c o n t r o l ter. Here you can switch from automatic to manual mode and move Setting values > Control mode Automatic > the vent into the desired position. You can use manual mode for Measurements > example when a sensor malfunctions. Control mode Automatic Manual Control mode Explanation Automatic Manual C203 maintains the temperature of domestic hot water at the setting value set by the user. LV K ä y t t ö v e d e n s ä ä t ö Asetusarvot Ohjaustapa LV Käsiajoasento Mittaukset Manual mechanical > Käsiajo > The position of the desired vent is set with the setting value ”HW Manual position.” 0% > > In mechanical manual mode the valve’s position is set from the actuator. To prevent the regulator from changing the position of the valve, the actuator’s power input must be disconnected. 4.3 Measurements DH Domestic hot water control -> Measurements The ”Measurements” menu under the circuit shows the measurements related to the circuit. All measurements linked to the regulator can be found in the Measurements menu at the root level (see page 7). 19