69 (70) User Manual M10 MultiController 9. Module Parameters Module parameters can be accessed on the “Module” tab of the Lonix PCT. Functionality of Network Variables: A command variable for the controller. Commands are carried out by entering a desired value to this variable from the following table: nci_Cmd: Value of nci_Cmd 10000 – 10019 65535 Function Browsing of active alarms Module RESET When browsing the alarms, the latest active alarm is read by entering value 10000 to nci_Cmd, the oldest with value 10019. Corresponding alarm details (object_id, priority, etc.) are shown in nvoAlarm variable of the Node Object and alarming point position string in nvoAlarmPos. Even though the alarms are shown in the alarm output variables no data is propagated to the LON network. Shows I/O-object specific data e.g. usage (operational) hours of DI-objects. See also chapter: “Tables on nvoTrend and nvi_x_Override variables”. nvoTrend: Configuration Parameters: Parameter Description Range Module Name This parameter is for the identification of the module. For example the COBA BOS Server application uses this information to identify alarming module. Six first characters of the parameter are included in the beginning of nvoAlarm variable when an object inside the module triggers an alarm. It is recommended that the value of this parameter is exactly the same as the module’s name in the LON database. 0…6 characters LONIX LTD www.lonix.com Teollisuuskatu 33 FI-00510 Helsinki, Finland Tel. +358 9 349 9853 Fax +358 9 349 9863 VAT 1043054-9 Trade Reg.No. 678.356