Data access using Modbus TCP/IP takes the form of a request for data by the master,
followed by a response from the slave indicating either success (response), or failure
(exception response) as shown in Figure 12-2. If no response is received this indicates
that the message has not been received or the node is unable to reply.
Figure 12-2 Modbus TCP/IP- request, response, exception
Function
Code
Response Data
PDU (Response)
Function
Code
Function Data
PDU (Request)
Exception Data
Getting
started
Function
Code
PDU (Exception Response)
Table 12.1 MBAP
Description
Transaction identifier MSB.
Transaction identifier LSB.
Protocol identifier MSB.
Protocol identifier LSB.
Length MSB.
Length LSB.
Unit identifier.
Security
Table 12.2 PDU
PDU
Diagnostics
Consists of
Function code, 1 byte
Request
Function data, > 1 byte
Function code, 1 byte
Response
Response data, > 1 byte
Exception Error code, 1 byte
Response Exception code, 1 byte
Quick
reference
If accessing one of the SM-Applications parameters (menus 7x, 8x or 9x) on a drive
with more than one SM-Applications module installed, the message will be routed to the
SM-Applications module installed in the lowest slot number, if this is undesireable then
the direct access parameters (menus 10x, 11x, 12x, etc) should be used.
Advanced
features
NOTE
Web page FTP/custom
Applications
basics
pages
The following tables document the structure of the MBAP and PDU, specifically the
functions of each data byte within the overall message structure.
Protocols
MBAP and PDU message structure
Byte
0
1
2
3
4
5
6
Safety
Mechanical Electrical
Introduction
information
installation installation
12.5.2 Data access