Download uk
Transcript
Installation 2.4.1.1 PCB Terminals and Fuses Terminal AC (2) BATTBATT+ S D C B A L/S (2) AUXAUX+ SW+ TAMP Z1 - Z8 T R AUXAUX+ Description Transformer AC in Standby Battery negative Standby Battery positive SAB Strobe switched negative SAB negative Supply SAB negative Tamper return SAB Bell switched negative SAB positive Supply Loudspeaker Auxiliary Supply negative Auxiliary Supply positive Switched Positive output Global Tamper loop Zone loops Keypad data Keypad data Auxiliary Supply negative Auxiliary Supply positive Note NOT for mains supply use for detectors use for detectors use for RKP(s) use for RKP(s) 1) A spare mains fuse is supplied in a clip adjacent to the mains terminal block. 2) Spare PCB fuses are supplied in a press-seal bag. Fuse F1 F2 F3 F4 F5 Description Battery fuse Bell & Strobe fuse L/S & Detector Auxiliary fuse RKP Auxiliary fuse Power Supply Output fuse Rating F1A, 250V, 20mm F1A, 250V, 20mm F500mA, 250V, 20mm F500mA, 250V, 20mm F1.6A, 250V, 20mm 1) When replacing a fuse always observe the specified rating and type - failure to do so is dangerous and will invalidate the warranty. Fuses should comply with IEC 127. 2) The press-seal bag must NOT be stored inside the panel. 2.4.2 Wiring the External Sounder and Strobe Always consult the manufacturer's connection instructions. The external sounder and strobe are connected to the five terminals labelled SAB on the control panel as follows: Terminal A B C D S INS 034-9 Description Permanent Positive Supply (+12V) Switched Negative to Activate Sounder Negative Tamper Return Permanent Negative Supply (0V) Switched Negative to Activate Strobe 9