1 ) Indoor room temperature sensor switching function
The following settings are needed when use the control by wired remote
controller temperature sensor/optional sensor.
( ...Factory setting)
Setting Description
No
Yes
Function No.
Setting No.
42
01
2 ) Room temperature control switching
This setting is used to set the room temperature control method when the
wired remote controller/optional sensor is selected by the Indoor room
temperature sensor switching function.
( ...Factory setting)
No
Yes
Controller sensor
Function No.
Setting No.
00
48
01
* If setting No. is “00” :
Room temperature is controlled by the sensors of both the indoor unit and
the wired remote controller/optional sensor.
* If setting No. is “01” :
Room temperature is controlled by the sensor of the wired remote control
ler/optional sensor.
$IWHUFRPSOHWLQJWKH)81&7,216(77,1*EHVXUHWRWXUQRIIWKHSRZHUDQG
turn it on again.
3 ) Connection state of op. sensor and Temperature sensor setting
The following settings are needed when switching the sensor. Perform
WKHVHWWLQJVLQ]RQHLQLWLDOVHWWLQJ)RUWKHGHWDLOVUHIHUWR=RQHLQLWLDO
setting".
‡ Connection state of op. sensor
( ...Factory setting)
Optional sensor 1
Optional sensor 2
Not in use
Not in use
In use
In use
Disable
Enable
Secondary controller sensor
Disable
Enable
11. MANAGEMENT FUNCTION
5HVWULFWVWKHRSHUDWLRQVRIIROORZLQJSRZHUVDYLQJIXQFWLRQVE\QRQDXWKRU
L]HGSHUVRQDQGKHOSVPRUHHQHUJ\HI¿FLHQWRSHUDWLRQRIWKHV\VWHP
:LWKWKHSDVVZRUGFRQWURORQO\WKHDGPLQLVWUDWRUFDQJHWDFFHVVWRWKH
function setting.
)RUWKHFRQWUROOHGIXQFWLRQVSHUIRUPWKHVHWWLQJFKDQJHLQ³0DQDJHPHQW
function” screen.
Settings Items:
Function
‡ Economy
‡ Set temp. auto return
‡ Set temp. range
(Set temp. auto return : Set temperature auto return)
(Set temp. range : Set temperature range)
)RUWKHGHWDLOVRQHDFKIXQFWLRQUHIHUWRWKHRSHUDWLQJPDQXDO
11.1. Password setting
Preset value of password is “0000”.
Change the password as necessary so that the setting change cannot be
done by other than the administrator.
The changed password should be managed properly by the administrator.
$SDVVZRUGGLJLWUHTXLUHGZKHQVHWWLQJXSD0DQDJHPHQWIXQFWLRQFDQ
be changed.
1
Mo 10:00
Date and time
Screen
Filter sign
R.C. sensor control
Room temp. display
Setting:
2
:KHQ>,QLWLDO@LVVHOHFWHGLQ>6XEPHQX@VFUHHQ³,QLWLDO´VFUHHQis
displayed.(QWHUFXUUHQWSDVVZRUGZLWKWKH>&XUVRUEXWWRQ@DQGSUHVV
the [Enter button].
Submenu [ 2/2 ]
Disable
Enable
Enable
Back:
* If setting "Disable" :
Remote controller temperature sensor cannot be used.
* If setting "Enable" :
Remote controller temperature sensor can be used.
Mo 10:00
Key lock select
Initial
Management
Secondary controller sensor
Disable
Child lock
Setting:
Monitor
3
6HOHFW>3DVVZRUGVHWWLQJ0DQDJHPHQW@LQWKH,QLWLDOVFUHHQDQG
press the [Enter button].
Initial
4 ) Setting record
‡ Record the setting change in the following table.
Mo 10:00
English
Language
°C
Temp. unit
Password setting (Management)
Setting No.
Indoor room temperature sensor
switching function
Back:
Filter sign
Room temperature control switching
‡ Record the connection state of op. sensor in the following table.
Optional sensor
Off
Off
Monitor
( ...Factory setting)
13
When [Menu button] is pressed twice while “Monitor” screen is dis
SOD\HGLWVZLWFKHVWRWKH³6XEPHQX´VFUHHQ
,I>0HQXEXWWRQ@LVSUHVVHGZKLOHWKH³6XEPHQX´VFUHHQLVGLVSOD\HG
the display returns to the “Monitor” screen.
Submenu [1/2]
‡ Temperature sensor setting
Setting Description
Timer
‡ On timer
‡ Off timer
‡ Weekly timer
‡ $XWRRIIWLPHU
Back:
* If setting "Not in use" :
Optional sensor cannot be used for room temperature sensor.
* If setting "In use" :
Optional sensor can be used for room temperature sensor.
Primary controller sensor
Memo
Primary controller sensor
00
* If setting No. is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting No. is “01” :
Room temperature is controlled by indoor unit temperature sensor/remote
controller unit sensor/optional sensor.
Setting Description
‡ Record the temperature sensor setting in the following table.
Memo
Optional sensor 1
Not in use
In use
Optional sensor 2
Not in use
In use
Setting:
Management