Download Installation / Service Manual
Transcript
Vitogas 050, ECD Series Technical Data Cut-away view (left side) Left view Front view B Vent connection Draft hood Boiler supply water 11⁄4˝ (water flows out) Ignition control 24V gas valve 24V vent damper Gas connection 2.5˝ (64) Burner manifold 120V power in 120V 4A max. output to pump 24V thermostat 26.00˝ (660) Transformer 12.25˝ (310) ECD-180/200 45.75˝ (1160mm) ECD-65 to 155 41.75˝ (1060mm) Boiler well for capillaries Boiler return water 11⁄4˝ (water flows in) 2.82˝ (72) A 11.00˝ (279) 17.50˝ (445) 19.75˝ (502) Boiler electrical requirements are 120V, 60 Hz, less than 12A Max. pump amperage is 4A. Use field supplied relay for pumps over 4A. Model CSA input DOE heating capacity CGA output Width “A” Vent Conn. “BØ” Water Content Weight AFUE* Steady State Efficiency ECD-65 65,000 Btu/h 19 kW 53,950 Btu/h 16 kW 350 mm 14˝ 5˝ 1 11⁄4˝ 3 2 9.9 ltr 2.6 USG 106 kg 233lbs 83.7% 83% ECD-80 80,000 Btu/h 23 kW 66,400 Btu/h 19 kW 350 mm 14˝ 5˝ 1 11⁄4˝ 3 2 9.9 ltr 2.6 USG 106 kg 233 lbs 83.5% 83% ECD-100 100,000 Btu/h 29 kW 83,000 Btu/h 24 kW 450 mm 173⁄4˝ 6˝ 1 11⁄4˝ 4 3 13.2 ltr 3.5 USG 130 kg 285 lbs 83.5% 83% ECD-115 115,000 Btu/h 34 kW 95,450 Btu/h 28 kW 450 mm 173⁄4˝ 6˝ 1 11⁄4˝ 4 3 13.2 ltr 3.5 USG 130 kg 285 lbs 83.5% 83% ECD-140 140,000 Btu/h 41 kW 116,200 Btu/h 34 kW 550 mm 213⁄4˝ 7˝ 1 11⁄4˝ 5 4 16.5 ltr 4.3 USG 157 kg 345 lbs 83.5% 83% ECD-155 155,000 Btu/h 45 kW 128,500 Btu/h 38 kW 550 mm 213⁄4˝ 7˝ 1 11⁄4˝ 5 4 16.5 ltr 4.3 USG 157 kg 345 lbs 83.4% 83% ECD-180 180,000 Btu/h 52 kW 149,400 Btu/h 44 kW 654 mm 253⁄4˝ 7˝ 1 11⁄4˝ 6 5 26.8 ltr 7.1 USG 192 kg 423 lbs 83.2% 83% ECD-200 200,000 Btu/h 58 kW 166,000 Btu/h 48 kW 654 mm 253⁄4˝ 7˝ 1 11⁄4˝ 6 5 26.8 ltr 7.1 USG 192 kg 423 lbs 83.0% 83% * With vent damper and intermittent pilot ignition kW figures are approximate Gas Conn. ⁄2˝ ⁄2˝ ⁄2˝ ⁄2˝ ⁄2˝ ⁄2˝ ⁄2˝ ⁄2˝ Water Conn. Cast Burners Iron Sections All sizes available with propane gas. For net IBR rating divide output by 1.15. Electrical requirement 120V, 60Hz, less than 12A Before operating this boiler/burner unit, make sure you fully understand its method of operation. Your heating contractor should always perform the initial start-up and explain the system and the need for regular inspection and maintenance. Boiler handling The boiler is shipped on a wooden pallet in a cardboard crate. Crate and wooden pallet must be removed. Vent damper is shipped separately. The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1 (latest edition). In Canada follow CAN/CSA–B149.1 or .2 Installation Codes (latest edition). Boiler location – Minimum clearances to combustibles (all measurements from boiler enclosure) Left side: 150 mm (6˝) Right side: 25 mm (1˝) Front: 150 mm (6˝) Top: 450 mm (18˝) Rear: 25 mm (1˝) Floor: Non-combustible Flue: 150 mm (6˝). Above clearances apply to all ECD boilers. These instructions must be placed in an envelope and affixed to the boiler. 3