Download Mini-MOD and Mini-Extension Installation Manual - Heat
Transcript
R Installation and Operation Instructions Mini-MIG Multiple Input Gateway with Temperature, Switch, and Pulse/counter inputs for Platinum and Gold Controls The digital display shows each output reading View Button scrolls through all inputs status LEDs indicate the power and communication status Overview Mini-MIG Multiple Input Gateway Power Comm T1 125 INPUT RATINGS: 115VAC 60Hz, 12VA MAX T2 72 T3 73 RESET VIEW T4 75 Use Copper Conductors Only. C US ENCLOSED ENERGY MANAGEMENT EQUIPMENT CAUTION: Risk of Electric Shock. LISTED 99RA DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS PWR Network L N N1 Input 1 Input 2 1 2 3 4 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 120VAC Power Input 3 Input 4 Input 5 Input 6 Connect to Platinum or Gold control Network terminals Input 7 Input 8 Pulse Input 9 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 The Mini-MIG is used with any Heat-Timer Remote Communication network or Internet control. The Mini-MIG simplifies the wiring and reduces the cost of individual Network sensors. The network can terminate in any of the following controls which have been equipped with the Internet or Remote Communications packages: MPC, MPCQ, HWR, HWRQ, SRC, or Multi-MOD. The MIG can accept Temperature, Switch, and pulse/counter (with Internet ready Platinum controls only) inputs. Any of the sensors types listed on the next page can be connected to the Mini-MIG. However, The pulse counters can only be utilized when connected to an Internet ready Platinum control. Wire to each Input Temp, Switch or counter WARNING All Heat-Timer controls are strictly operating controls. They CANNOT be used as limit controls. All boilers must have all safety and limit controls required by code. It is the responsibility of the installer to verify that all the safety and limits are working properly before the Mini-Mod is installed. 2 Heat-Timer Corp. Possible Sensor Types to connect to Mini-MIG Part# Type 904001-00 Space Room Space Sensor in plastic enclosure to be wall mounted Name STARTUP 904220-00 Temperature Outdoor, Strap-On, or Immersion Sensor (3-in-1 Sensor) 904250-00 Temperature Brass Tube Sensor ⅜” diameter with concave surface. 904022-00 Temperature UV, Corrosion, and Moisture Resistant Sensor 904112-00 Temperature Stainless Steel Sensor with Tapered Tip ¼" x 6" 904021-00 Temperature Stainless Steel Sensor with Round tip ¼" x 6" 904060-01 Switch Float (Sump Pit) Assembly with 1" Clamp- provides Dry Contact closure 904060-00 Switch Float (Sump Pit) Assembly with 1 ½" - provides Dry Contact closure Size 1" 1 ½" 904060-02 Switch Float (Sump Pit) Assembly with 2" - provides Dry Contact closure 380001-00 Count (Input #16) Water Meter Counter ½" NPT 150 PSI, 200˚F Y ½" 2" 380002-00 Count (Input #16) Water Meter Counter ¾" NPT 150 PSI, 200˚F Y ¾" 380003-00 Count (Input #16) Water Meter Counter 1" NPT 150 PSI, 200˚F Y 1" 380004-00 Count (Input #16) Water Meter Counter 1 ¼" NPT 150 PSI, 200˚F Y 1 ¼" 380005-00 Count (Input #16) Water Meter Counter 1 ½" NPT 150 PSI, 200˚F Y 1 ½" 380006-00 Count (Input #16) Water Meter Counter 2" NPT 150 PSI, 194˚F Y 2" 380010-00 Count (Input #16) Water Meter Counter ½" NPT 232 PSI, 248˚F Y ½" 380011-00 Count (Input #16) Water Meter Counter ¾" NPT 232 PSI, 248˚F Y ¾" 380012-00 Count (Input #16) Water Meter Counter 1" NPT 232 PSI, 248˚F Y 1" 380013-00 Count (Input #16) Water Meter Counter 1 ½" NPT 232 PSI, 248˚F Y 1 ½" 380020-00 Count (Input #16) Water Meter Counter 2" NPT 232 PSI, 248˚F Y 2" 380021-00 Count (Input #16) Water Meter Counter 3" NPT 232 PSI, 248˚F Y 3" 380022-00 Count (Input #16) Water Meter Counter 4" NPT 232 PSI, 248˚F Y 4" 380023-00 Count (Input #16) Water Meter Counter 6" NPT 232 PSI, 248˚F Y 6" 380024-00 Count (Input #16) Water Meter Counter 8" NPT 232 PSI, 248˚F Y 8" Installation The Mini-MIG consists of three primary enclosure components. • he Enclosure Display Module: contains the display, buttons, LEDs and electric wiring terminals. Wiring terminals are of the T plug-in type to ease installation and removal. The Display Module mounts to the Enclosure Display Module base using two screws. NOTE: Never unscrew the PCB board from the Enclosure Display Module. If there was a problem with the control, the complete Enclosure Display Module must be return to factory for inspection and repair. • he Enclosure Base: contains the holes to mount and hold the control against the T wall or any flat surface. All other enclosure components mount on the base. The bottom section of the Enclosure Base contains the wiring chamber with knockouts on the bottom to ease the installation. • he Enclosure Wiring Cover: covers the wires from the external environment. T It has two screws to hold it to the base and a hole to secure a lock on the wiring enclosure. A plastic web that separates the wiring chamber into high and low volt sections has been provided. Enclosure Wiring Cover Hole for optional lock (not supplied) Enclosure Base Bottom knockouts Mini-MIG Installation Manual Mounting the Enclosure 3 Mounting Base •Select a location near the equipment to be controlled. •The surface should be flat, and be sufficiently wide and strong to hold the control. •Keep the control away from extreme heat, cold, or humidity. Ambient operating temperature is from 20 to 130°F. •Remove the Enclosure Wiring Cover from the control enclosure by removing the two bottom screws. •Remove the Enclosure Display Module by removing the middle screws. •Screw the Enclosure Base to the surface through the upper and lower mounting holes on the back of the enclosure. •Replace the Enclosure Display Module and replace the middle screws. •Do not replace the enclosure wiring cover until all wiring is done. Dip Switch Setting O 1 2 N The Mini-MIG can accept inputs from temperature sensors, Dry Contact closure, Display Mounting Screws Wiring Cover Mounting Screws and a pulse/count sensor (input 16 only when activated with an Internet ready control). Input#16 Set as Temp/Switch Active •However, to activate input #16 to work as a pulse/count sensor, Dip Switch 1 must be set to OFF and Dip Switch 2 must be set to ON. In addition, the Startup menu option CNTR must be set to "Y". See Startup Settings on page 4. Input#16 Set as Pulse/Count Active •To activate input #16 to work as a temperature/switch sensor, Dip Mini-MIG Switch 1 must be set to ON and Dip Switch 2 must be set to OFF. Wiring Comm Multiple Input Gateway O 1 2 N O 1 2 N Power T1 125 INPUT RATINGS: 115VAC 60Hz, 12VA MAX T2 72 T3 73 T4 75 Use Copper Conductors Only. Wiring the Power (Terminals 1 and 2) •Bring the 120VAC 60Hz power wires through the leftUS C VIEW RESET WARNING bottom Knockout of the enclosure. CAUTION: Risk of Electric Shock.enter the enclosure through a different 1 voltages must •Class 1 voltages must enter the enclosure throughLISTED a Class 99RA opening from any Class 2 voltage wiring. Heat-Timer recommends different opening from any Class 2 voltage wiring. installing a surge suppressor on the power source to the Mini-MIG. •Connect the hot line to terminal marked L 1. DO NOT APPLY ANY VOLTAGE •Connect the neutral line to the terminal marked N 2. TO INPUT TERMINALS PWR Network •Heat-Timer recommends installing a surge suppressor on the power source to the MiniPulse Input 9 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 L N N1 MOD. ENCLOSED ENERGY MANAGEMENT EQUIPMENT 1 2 3 4 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 Wiring temperature Sensors A1 DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS T A2 A3 Switch Sensor SYSTEM TEMP Temp Sensor Line MPC Platinum Wiring Switch Sensors Neutral •Only use Heat-Timer Gold sensors. 120VAC up to 500' using a shielded 2-conductor cable (Belden •The sensor wires can be extended Power Source #8760 or equivalent). DO NOT ground the shield at the sensor but do connect at the MiniMIG using one of the terminals marked with an “O”. •Do not run sensor wires in conduit with line voltage wiring. •Temperature sensors haveINPUTS no polarity. Pulse Counter SHUTDOWN •The Switch sensor signal must be a Dry Contact only. No voltage can be placed across the Switch sensor input terminals •Do not run sensor wires in conduit withPROVE line voltage wiring. ADJUST ALL SENSORS MUST BE GOLD SERIES SENSORS A4 A5 A6 A7 MON 12/28/04 10:43Am NETWORK Wiring Pulse/Count Sensors (Input#16 Terminals 37,38) Only) Cycle On PRESS TO A8 A9 Cut= OD= AUX 0 SELECT Day pulse/count sensor •The signal must be INPUT a Dry Contact only. No voltage can be placed across the Switch sensor input terminals oF oF 31• SYS= 148 OUT Do not run sensor wires in conduit withTEMP line voltage wiring. BACK •Make sure that Dip Switch 1 is OFF andAUXDip Swith 2 is ON. TEMP 0 •Startup CNTR must be set to "Y". 55oF A10 A11 T A12 A13 T A14 A15 HELP PREV. DAY A17 (DEL) A18 OUTPUT SYS AUX CLOCK OPTION 1 OPTION 2 T AUX TEMP 1 T AUX TEMP 2 A16 NEXT OPTION 3 MANAGEMENT EQUIPMENT CAUTION LISTED 99RA Heat-Timer Corp. To utilize the Mini-MIG, it must be connected to a communication ready Platinum or Gold control through the Network terminals. This will provide the control with access to the Mini-MIG sensor data. •The Mini-MIG has two sets of network terminals. Either set can be connected to the Platinum/Gold control Network terminals. •The second set of Mini-MIG Network terminals can be used to connect to other network sensors. •Each sensor must be configured using the Cremote communication of the specific control (either O R P O R A T I O N MPC through Visual Gold or the Internet). When configuring each sensor, the proper sensor type must be selected. Platinum 120VAC Power Source PWR Network L N N1 Input 1 In 1 2 3 4 7 8 9 Line Connecting to the Platinum or Gold Controls Neutral 4 R INPUTS DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS ALL SENSORS MUST BE GOLD SERIES SENSORS Startup Settings SELECT enters menus or accepts changes ADJUST selects menu items or changes settings MON 12/28/04 Cycle T A2 A3 SHUTDOWN A5 PROVE A7 10:43Am SYSTEM TEMP A4 A6 ADJUST MENU FUNCTIONS A1 NETWORK A8 On A9 PRESS TO AUX INPUT 0 oF SELECT Day to function •Selecting "N" from the Startup menu using the "View Button" will Cut= allow55the MIG HEAT-TIMER OUT CORP. OD= 31oF SYS= 148oF with a Platinum or a Gold control using Visual Gold Software. No counter will be available TEMP V.102 >[y]CNTR BACK in this setting. AUX TEMP 0 •Selecting "Y" from the Startup menu using the "View AUTOButton" will allow the MIG to function U LThis C US AUX with a Platinum control using the Internet. will allow the user to configure Input 16 as a pulse counter or a temperature or TEMP 1 HELP NEXT PREV. DAY BYPASS switch. See Dip Switch Settings on page 3. AUX BACK returns to previous menu DAY PREV./NEXT A10 selects next day A11 steps through output status A12 A13 T T A14 A15 R A17 (DEL) LISTED 99RA Buttons T A16 ENCLOSED ENERGY MANAGEMENT EQUIPMENT A18 OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS OUTPUT AUX CLOCK SYS OPTION 1 T TEMP 2 OPTION 3 OPTION 2 ALERT The Mini-MIG can control a pulse counter ONLY when INPUT RATINGS: 115VAC 60Hz 30VA MAX •The " View" button scrolls the display through all the inputs and their connected to an Internet ready Platinum control. The Startup option must be set to "Y" in this case. values. •The " Reset" button tests the network communication components and refreshes the display data. USE COPPER WIRE, CLASS 1 WIRE ONLY SAFETY GROUND MUST BE CONNECTED LINE Mini-MIG Specifications 3 NEUTRAL 2 4 5 6 B R W MOTORIZED VALVE 7 8 BURNER 9 10 SYSTEM 11 12 AUX CLOCK 13 14 OPTION 1 15 16 OPTION 2 17 18 OPTION 3 Voltage Input: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 VAC 60 Hz Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 VA Max Operating Temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20°F to 130°F Operating Humidity: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20% to 80% Display: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alphanumeric (2 rows x 16 char. each) LED: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (1) Power, (1) Communication Inputs: . . . . . . . . . . . . . Total of 16 inputs that can accept Temperature (All), Switch (All), and Count Sensor (input 16) Buttons: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . View (scrolls through inputs), Reset (tests Communication) Communication: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Network communication ports Temperature Sensor Ranges: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - minus 35°F to 250°F Dimensions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11"W x 9" H x 3 ¾" D Weight: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 pounds MADE IN U.S.A. R C O R P O R A T I O N ROUTE SENSOR AND AUXILIARY WIRES THROUGH THIS KNOCKOUT ONLY 20 New Dutch Lane, Fairfield, NJ 07004 973-575-4004 • Fax 973-575-4052 • http://www.heat-timer.com 059053-00 Rev.B