6-5 Explanation of Each Parameter No.
Writing Into Multiple Coils [0Fh]
Rewrites consecutive multiple coils.
Example) Change the statuses of multi-function input terminals S1 to S7/EB of the
Inverter with the slave address "1".
Change multi-function input terminals S1 to S7/EB to the statuses shown in the table below.
Function name
Data
Coil No.
0007h
0008h
0009h
000Ah
000Bh
000Ch
000Dh
Multi-function input terminals
S1
S2
S3/GS1
S4/GS2
S5/TH
S6
S7/EB
Terminal status
ON
ON
ON
OFF
ON
OFF
OFF
Query:
No.
Field name
1
Slave address*1
2
Parameter No.
Example
(Hex)
01
0F
Coil start address
00
4
Coil start address (LSB)*2
06
5
Number of coils (MSB)
00
6
Number of coils (LSB)
07
7
Number of bytes
02
8
Change data (MSB)
17
9
Change data (LSB)
00
10
CRC-16 (MSB)
06
CRC-16 (LSB)
98
(Coil address) = (Coil number) − 1
6
Communication Function
3
(MSB)*2
17h = 0001 0111
Input terminal S1
Input terminal S7/EB
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6-14