Download User's Manual - Support
Transcript
operation2.book Page 91 Wednesday, January 7, 2004 10:04 AM Section 5 DETAILED SETTINGS Two-point teaching Performs measurement on two samples and uses the intermediate value of the two measurement results to set threshold values. Two-point teaching is useful when you want to detect subtle differences between the standard sample and defective samples. Sensor head Sensor head Teaching point A Standard sample Teaching point B Defective sample The threshold can be calculated by the following equation. Threshold = (Teaching point A + Teaching point B) / 2 teaching measurements. Setting Teaching point A 1. Set the teaching point A by following steps 1. to 4. of the position teaching procedure. SUB Setting Threshold Values 2. Place a defective sample in position. Section 5 Entering Threshold Values Hold, trigger mode, and scaling settings that have been made before teaching are reflected in the The main display value changes. 3. Press the ENT Key for at least three seconds and then release. SUB The measured value at the point that the ENT Key is released will be set as the value for teaching point B to set threshold value. This threshold value will be shown on the sub-display. When [ERRLH] or [ERRHL] is displayedp.89 The threshold values set using two-point teaching can be changed using direct input. This is useful when setting judgement tolerances for measured values. p.89 ZX-L-N User’s Manual 91