Download Installation Manual
Transcript
SMA Solar Technology AG 6 Electrical Connection 6.5.2 Extension of the Deactivation Limits The deactivation criteria (voltage, frequency) are specified by the country parameters. Sunny Tripower inverters have the additional country data set "MVtgDirective". This parameter expands the deactivation limits of the inverter for voltage and frequency to a maximum/minimum. This country setting may only be selected if the plant or the inverter is operated with external three-phase decoupling protection, which will automatically disconnect the inverter from the electricity grid if non-permissible voltage and frequency values occur. Device protection is still guaranteed. Danger to life due to electric shock if external decoupling protection is missing With the country setting "MVtgDirective", the inverter may only be operated with an external three-phase decoupling protection device which complies with the country-specific requirements. Without such external decoupling protection, the inverter will not disconnect from the electricity grid when the standard requirement is exceeded. • Install external three-phase decoupling protection. Installation Manual STP8-17TL-IA-en-31 51