DriveControl HC-EC100 / HC-EC110 Product information External speed setting Apart from the potentiometer on the DriveControl, there are other ways to set the speed. Hint When the DIP switch settings ON / OFF are stated, both settings are possible for the shown wiring (for the meaning of the settings see "DIP switches", page 14). Direction of travel ROLLER DRIVE External speed set by potentiometer Speed analog (input) Ext. Pot. + Sensor1 in GND +24 VDC GND (input) +24 VDC (input) to downstream ZPA card to upstream ZPA card +24 VDC GND Potentiometer 10 k Ω Pot. at minimum equals 10% of rated speed for HC-EC100 and 33% of rated speed for HC-EC110 DIP switch settings: • SW5: ON / OFF (If SW5 is ON, speed setting is transferred downstream.) • SW4: ON / OFF (If SW4 is ON, speed setting is transferred upstream.) • SW3: ON / OFF • SW2: ON / OFF • SW1: ON / OFF Direction of travel ROLLER DRIVE External speed set by PLC Speed analog (input) Sensor1 in GND +24 VDC GND (input) +24 VDC (input) to downstream ZPA card +24 VDC GND to upstream ZPA card 0 - 5 VDC GND PLC analog speed output (0-5 VDC) 0 V = 10 % of rated speed for HC-EC100 0 V = 33 % of rated speed for HC-EC110 5 V = 100 % of rated speed DIP switch settings: • SW5: ON / OFF (If SW5 is ON, speed setting is transferred downstream.) • SW4: ON / OFF (If SW4 is ON, speed setting is transferred upstream.) • SW3: ON / OFF • SW2: ON / OFF • SW1: ON / OFF Version 1.2 (02/2009) en Original language 19