Download User Manual
Transcript
User Manual v1.9 Digital input Update time, off state 1 day Update time, on state 15 minutes Input is expected to be on twice per year for 4 hours No. of change messages per year = 2 (twice per year) * 2 (on to off and off to on) = 4 No. of “off” update messages per year = 364 (approximately) No. of “on” update messages per year = 2 (twice per year) * 16 (4 hours @ 15 min update) = 32 = 4 + 364 + 32 Total messages for digital input Pulse input Update time 1 day = 400 Sensitivity 50 Average pulse rate is 1 pulse per hour, with peak rate of 20 per hour, for 10 hours, three times per year. No. of change messages (normal rate) = 0 (time for 50 pulses is more than the update time) No. of change messages (peak rate) = 3 (three per year) * 200 (20 per hr for 10 hrs) / 50 = 12 No. of update messages per year = 363 (approx) Total messages for pulse input = 12 + 363 Analog input = 375 Sample time 1 hour Warm-up time 5 secs Sensitivity Update time 1 day 3% Average changes of >3% is twice per day No. of change messages per year = 2 (twice per day) * 365 = 730 No. of update messages per year = 0 (always be a change message each 1 day) Total messages for analog input = 730 Total input messages per year = 400 + 375 + 730 = Power consumed in transmissions = 0.005 * 1505 * 2 (2 transmissions per message) = 1505 15 mAHr per year Power for analog loop supply (assume average loop current is 12mA) No. of analog measurements per year Power for analog loop supply Manual WI-I/O 9-K v1.9 = 365 days * 24 hours * 1(sample time) = 8,760 = 0.012 (from above table) * 5 (warm-up time) * 8,760 = 526 mAHr per year Page 21