Download User Manual
Transcript
1+" or "AI 2+", etc) should be connected to "+24V". Externally powered loops may be connected by connecting the input between "AI 1+" and “AI 1-” for analog input 1 or "AI 2+" and “AI 2-” for analog input 2, and so on for other inputs. Common mode voltage may be -0.5V to 27V. Shielded cable is recommended for analog I/O loops to minimise induced noise and Radio Frequency Interference (RFI). The shield of the cable should be connected to earth at one of the cable only. The use of shielded wiring inside an enclosure containing a module is also recommended. To connect an AI on the WI-I/O 9-x to an analog signal from a PLC or DCS output, check the internal circuit of the output carefully as different devices use different ways to create an analog signal. The following diagram shows two ways of connecting. +V Current source output AO -V + +24V _ - AI +AI PLC COM WI-I/O 9 +24V +AI AO Current sink output - AI COM COM WI-I/O 9 Note: 1. AI must be within 27V of COM. If terminal voltages exceed this, a loop isolator must be used. 2. COM on the WII/O is connected to ground/earth. If the COM of the PLC cannot be grounded, then a loop isolator must be used. PLC 2.4.5 Analog Outputs (WI-I/O 9-1 and WI-I/O 9-3) The ”-1” module provides two 4 - 20 mA DC analog outputs for connecting to instrument indicators for the display of remote analog measurements. The ”-3” module provides eight 0 - 20 mA DC analog outputs. Each analog output is a "sink" to common. +24V AO 1 WI-I/O 9 _ + COM A 24VDC supply is available on the module for powering the analog output loop (max external loop resistance 1000 ohms). In this case, the analog loop is connected between a "+24V" terminal and "AO 1" (for the first analog output) or "AO 2" (for the second analog output), and so on for the other output WI-I/O 9-x_WI-I/O-EX-1-S-x 2.16 Page 21