Technical Specifications Housing Height Width Depth Weight Potential equalisation Earthing IP protection category LED display Temperature range in operation Humidity range in operation Storage temperature range Voltage connection: Power supply Fuses Power input Detector connection Plastic covering with metal trim piece 1 U, approx. 4.45 cm approx. 13.6 cm approx. 12.9 cm approx. 0.35 kg without packaging Not required, because 24 VDC protective low voltage Not required, because 24 VDC protective low voltage IP 40 to EN 60529 blue / white, 122 x 23 Pixels +5 °C to 45 °C / +41 °F to 113 °F 5% to 95% relative humidity, non-condensing -20 °C to 60 °C / -4 °F to 140 °F 1x, DC 24 V, max. current 3 A SELV Fine fuse: T 3 A, 250 V, UL approval 50 mA 1x, RJ12 sockets, shielded Installation Instructions The Rittal CMC-TC Display Unit II must be installed in an enclosure or housing system that provides additional protection from external influences. The cable lengths must not exceed the lengths given in the technical specifications in order to avoid losses due to unnecessary lengths of cables. Attention must be paid to maintaining the permitted ambient temperature and humidity ranges, as well as the IP protection category as required for the specific application. The appropriate information is contained in the technical specifications (page 7). 7 / 17