VAV VV550 Controller Device Home Tabs: Instructions the configured reheat enable setpoint. The range for the Reheat enable setpoint for Hydronic heat is 70°F to 200°F (21.11°C to 93.33°C) The range for the Reheat enable setpoint for Electric heat is 70°F to 100°F [21.11°C to 37.78°C]). Reheat Priority: Choices are Local and Remote. This area is available only if the controller is using space temperature control. • Local: Select this option to use local reheat before remote reheat. • Remote: Select this option to use remote reheat before local reheat. Fan Configuration Fan Present: This dialog box should be checked if the unit has a fan. Rover automatically changes the entry to 0 (None). When the value of this field is not None, the configuration of Output 3 is set to Normally Open. Fan Type: Select the type of fan used by the VAV VV550 Controller. If you edit the unit type field, Valid Selections: Parallel, Series. Parallel Fan Control: This entry will determine if a parallel fan will be controlled based on zone temperature or on flow conditions. The entry field on this line will disappear if the unit does not have a parallel fan. Parallel Fan Setup: If "Parallel fan control" has been edited to "Space Temperature" the fan control offset will be entered as a temperature offset (.3° - 8°F) which will be added to the heating set point. If "Parallel fan control" has been edited to "Primary Flow" this line will be entered as a percent (0 to 100%) Note: See the Sequence of Operations section of this manual for details on parallel fan operation. Box Setup: Select the proper Setup type. The selectable item is either a "Trane F style" unit manufactured by Trane or "Generic" if the VV550 controller is mounted on some one else's VAV unit. The unit type information is maintained in the controller's EEPROM. When Trane F style unit is selected it will also show the inlet size and type in inches. The entry field on this line will disappear if the unit does not have Trane F style unit selected Note: See CNT-PRC003-EN if retrofitting a VV550/1 controller onto someone else's VAV unit. 58 VAV-SVP01A-EN