Section 5-18 Data Conversion Signed Binary Data BCD(24) cannot be used to convert signed binary data directly to BCD. To convert signed binary data, first determine whether the data is positive or negative. If it is positive, BCD(24) can be used to convert the data to BCD. If it is negative, use the 2’s COMPLEMENT – NEG(––) instruction to convert the data to unsigned binary before executing BCD(24). Refer to page 29 for details on signed binary data. Flags ER: S is greater than 270F. Indirectly addressed DM word is non-existent. (Content of ∗DM word is not BCD, or the DM area boundary has been exceeded.) EQ: ON when the result is zero. 5-18-4 DOUBLE BINARY-TO-DOUBLE BCD – BCDL(59) Ladder Symbols Operand Data Areas S: First source word (binary) BCDL(59) @BCDL(59) S S R R IR, SR, AR, DM, HR, TC, LR R: First result word Limitations IR, SR, AR, DM, HR, LR If the content of S exceeds 05F5E0FF, the converted result would exceed 99999999 and BCDL(59) will not be executed. When the instruction is not executed, the content of R and R+1 remain unchanged. S and S+1 must be in the same data area as must R and R+1. Description BCDL(59) converts the 32-bit binary content of S and S+1 into eight digits of BCD data, and outputs the converted data to R and R+1. Binary S+1 S BCD R+1 R Signed Binary Data BCD(24) cannot be used to convert signed binary data directly to BCD. To convert signed binary data, first determine whether the data is positive or negative. If it is positive, BCD(24) can be used to convert the data to BCD. If it is negative, use the DOUBLE 2’s COMPLEMENT – NEGL(––) instruction to convert the data to unsigned binary before executing BCD(24). Refer to page 29 for details on signed binary data. Flags ER: Content of R and R+1 exceeds 99999999. Indirectly addressed DM word is non-existent. (Content of ∗DM word is not BCD, or the DM area boundary has been exceeded.) EQ: 182 ON when the result is zero.
Related documents
Emerson Universal-R Technical data
C200HX/HG/HE Manuel d`utilisation - Support
SYSMAC PROGRAMMABLE CONTROLLERS C200H (CPU01
Selectron LD-007 Programming instructions
sysmac cqm1 automate programmable manuel de
IDSC-C1DR/C1DT-AE ID Controller User's Manual
sysmac c200hx/c200hg/c200he automates programmables
Avaya Activity Reporter Client Version User's Manual
From C200H to CS1
Replacement Guide From CJ1M/CJ1G to CJ2M
ESET Mail Security for Microsoft Exchange Server
Using BIOS