Download Emerson 644 User's Manual
Transcript
Reference Manual 00809-0400-4728, Rev AA June 2011 WIRING Rosemount 644 All power to the transmitter is supplied over the signal wiring. Use ordinary copper wire of sufficient size to ensure that the voltage across the transmitter power terminals does not drop below 9 Vdc. If the sensor is installed in a high-voltage environment and a fault condition or installation error occurs, the sensor leads and transmitter terminals could carry lethal voltages. Use extreme caution when making contact with the leads and terminals. NOTE Do not apply high voltage (e.g., ac line voltage) to the transmitter terminals. Abnormally high voltage can damage the unit. (Sensor and transmitter power terminals are rated to 42.4 Vdc. A constant 42.4 volts across the sensor terminals may damage the unit.) The transmitters will accept inputs from a variety of RTD and thermocouple types. Refer to Figure 2-5 on page 2-7 when making sensor connections. Refer to Figure 2-6 on page 2-8 for FOUNDATION fieldbus installations. Use the following steps to wire the power and sensor to the transmitter: 1. Remove the terminal block cover (if applicable). 2. Connect the positive power lead to the “+” terminal. Connect the negative power lead to the “–” terminal (see Figure 2-7). 3. Tighten the terminal screws. When tightening the sensor and power wires, the max torque is 6-in.-lbs (0.7 N-m). 4. Reattach and tighten the cover (if applicable). 5. Apply power (see “Power Supply”). Figure 2-5. Transmitter Power, Communication, and Sensor Terminals 644H Sensor Terminals Communication Terminals 1 2 3 4 Power Terminals 2-7