Download Calculated Industries ElectriCalc Pro
Transcript
(cont’d) Wire Resistance (Wire Res) — Displays the actual Resistance per 1,000 Feet of the Wire Size in based on NEC Chapter 9, Table 8. Grounding Conductor Keys Ground — Used to find the Grounding electrode conductor size for AC systems based on NEC Table 250.66 and an entered or calculated service-entrance conductor (largest size). Only actual Wire Sizes are considered valid entries. ♦ First Press Calculates the copper Grounding electrode conductor size if you have entered a valid Wire Size. ♦ Second Press Displays the aluminum Grounding electrode conductor size. ♦ Third Press Displays the Circular Mil area used to calculate the Grounding electrode conductor size. ♦ Fourth Press Displays the NEC table referenced for the calculation. Equipment Ground (EqGrnd) — This function uses NEC Table 250.122 to calculate the minimum equipment Grounding conductor size, given an entered Amperage rating or setting for an over-current device up line. Note: This function deviates from the NEC Table 250.122 in that 1250 MCM AL is used instead of 1200 as specified in NEC Table 250.122. ♦ First Press Displays the copper Grounding conductor size for the entered Amp rating. 12 — ElectriCalc® Pro