2 CONTROLS AND INDICATORS CONTROL PANEL The ONLINE (green) LED illuminates in a steady state when the UPS is on and the inverter is providing the output power. The ONLINE LED will extinguish when operating in the Battery mode. The LINE (green) LED illuminates in a steady state when the UPS is connected to Utility Power and there is an acceptable AC voltage present. The LINE LED will extinguish when operating in the Battery mode and if the Utility voltage is not present. The LINE LED will flash when the Utility voltage or frequency is out of the Bypass mode range. The BYPASS (yellow) LED will be flashing when the UPS is operating in the Bypass mode. The BYPASS LED will extinguish when operating in the On-Line and the Battery modes. The FAULT (red) LED illuminates in a steady state when the UPS detects an internal fault and is not functioning properly. The FAULT LED is extinguished when the UPS is operating properly. The LOAD (yellow) LED illuminates is a steady state when the UPS is operating in the On-line or Bypass modes. The LOAD LED indicates the Battery/Load Capacity bar graph (4-LEDs) represents the output load capacity. The LOAD LED will extinguish in the Battery mode. The OVERLOAD (red) LED illuminates in a steady state when the output load has exceeded the full load rating of the UPS. The OVERLOAD LED will extinguish when the output load has not exceeded the full load rating of the UPS. The BATT (yellow) LED illuminates is a steady state when the UPS is operating in the Battery mode. The BATT LED indicates the Battery/Load Capacity bar graph (4LEDs) represents the battery capacity. The BATT LED will extinguish in the On-Line and the Bypass modes. 5