Download SERVICE MANUAL
Transcript
Item 8-2. Operation Mode and Control Method Operation flow and applicable data, etc. 4) Cooling operation Pressing the [ZONE1, 2] button and then [OPERATION MODE] starts a cooling operation. 1) Operation start condition Pressing the [ZONE1, 2] button and then [OPERATION MODE] starts a cooling operation. TWI Heat pump operation (cooling) TSC_F (Temperature set with 2) Operation mode selection An operation mode is determined according to the temperature of TWI sensor. d zone Diff : 2k remote controller) e zone TSC_F Thermostat off operation • Heat pump operation selection *1 When TWI TSC_F (d zone in the right figure) is met, the heat pump operation is selected. • Thermostat status "OFF" When TWI < TSC_F (e zone in the right figure) is met, the thermostat status "OFF" is selected. TSC is a cooling temperature set with the remote controller 3) Operation stop condition When either of the following conditions is met, the cooling operation stops. • The remote controller gives a stop instruction. • The operation is switched to heating. *1: When the outside temperature is 10°C or below, cooling does not start even if the TWI temperature falls into "d zone". Related FC FC No. Setting item Default Setting available range 1: Not permit 0: Permitted Upper limit of cooling setting temperature 25 20-30°C Lower limit of cooling setting temperature 10 10-20°C 02 Cooling mode availability 18 19 5) Simultaneous operations of "hot water supply" and "heating" At the time of "Hot water supply" and "Heating" simultaneous operation, the operation mode is select as follows depending on the outside air temperature. • f zone Operation with hot water supply priority A heat pump operation is performed in the hot water supply side, and a heating operation in the heating side. • g zone Operation with heating priority A heat pump operation is performed in the heating side, and a cylinder heater operation in the hot water supply side. TO Hot water supply heat pump priority operation 0 (FC22) Heating heat pump priority operation -20 Heater operation f zone Diff : 5deg g zone Diff : 5deg h zone *3 Operation mode by zone Zone Hot water supply side f Heat pump *2 Heating side Stop *2 g Heater Heat pump h Heater *3 Heater *3 *2: Note that after a heat pump operation for "Hot water supply" is selected in f zone, when the operation moves to a heater operation for "hot water" and then 5 minutes has passed (Hot water supply operation in b zone), the operation mode changes as follows. Zone Hot water supply side Heating side f' Heater Heat pump When TTW 45°C (FC: changeable) is met, the operation ends f' zone and returns to f zone. *3: If the h-zone operation starts while external temperature is higher than -20°C, the h-zone operation continues for 60 minutes. 50