Download SERVICE MANUAL
Transcript
Item 8-4. Outdoor unit control Operation flow and applicable data, etc. 5-2) Hot water supply and heating fan control 1) The TE sensor, TO sensor and operation frequency control the outdoor fan. (The minimum W1 to the maximum are controlled according to the table below.) 2) For 3 minutes after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After that, the fan is controlled according to the TE sensor temperature. 3) If TE 24°C continues for 5 minutes, the operation stops. No error code is displayed for this; the status is the same as the usual thermostat off. The operation restarts after 150 seconds. This intermittent running is not abnormal. NOTE It TO < -5°C and the heat-pump was thermo-off, the out-door fan motor (up/down) continue to run 10 mins with W3 rotation. TE [°C] -2 tap/20 secs (to W1) Stop time count 24 -2 tap/20 secs (to W1) 21 -1 tap/20 secs (to W1) 18 Number of revolutions hold 15 + 1 tap/20 secs (Up to the maximum tap for each zone) For 803H-E Temperature range Less than 20 Hz 20 Hz or more to less than 45 Hz 45 Hz or more Maximum Maximum Maximum TO W7 W8 W9 5°C TO < 10°C W9 WB WD -3°C TO < 5°C WD WD WE -10°C TO < -3°C WE WE WE TO < -10°C WF WF WF TO abnormal WF WF WF Less than 20 Hz 20 Hz or more to less than 45 Hz 45 Hz or more Maximum Maximum Maximum TO W7 W8 W9 5°C TO < 10°C W9 WA WA -3°C TO < 5°C WA WA WB -10°C TO < -3°C WB WB WB 10°C For 1103H-E Temperature range 10°C TO < -10°C WD WD WD TO abnormal WD WD WD Less than 20 Hz 20 Hz or more to less than 45 Hz 45 Hz or more Maximum For 1403H-E Temperature range Maximum Maximum TO W7 W8 W9 5°C TO < 10°C W9 WA WB -3°C TO < 5°C WB WB WC -10°C TO < -3°C WC WC WC 10°C TO < -10°C WD WD WD TO abnormal WD WD WD 76